In the coordinate system moving the mouse, click the left button, can change the
scanning center, users estimate the position of the scanning center based on the impedance
characteristics.
2. [Scanning radius]
Full 360 -degree scan, scanning radius determine the scanning range, the scanning
radius should be larger than the impedance tuning value.
3. [Scanning step]
Expressed with impedance, is the step of scanning center from the top of the scanning
radius
4. [Scanning range]
100% means that from the top of the scanning radius to the scan center, 50% indicates
half the radius to scanning from the top of the scanning radius, thus reducing test time.
5. [Fault type]: AN,BN,CN
;
AB, BC and CA 6 options.
6. [Short circuit current]: generally 5A.
7. [Normal state time]: generally 2 seconds.
8. [Fault time]: 1 second.
9. [Zero sequence coefficient]: 0.67.
10. [Switching value]: contact 1, normal open.
11. Wring: