background image

Operating Manual 

“Warm N Dry”

 

 

 

www.hvsolutions.com.au 

12 of 12 

 

Copyright  2010 

Appendix B - Heat Recovery Calculations 

The amount of heat or loss that can be contributed to the home is dependant upon the following 
factors: 

 

Outside temperature and  atmospheric pressure which effects the “Air Density” 

  Roof temperature (sun and roof structure etc) 

  House temperature (thermal mass, insulation and other heat sources/losses) 

  Air flow (fan speed and capacity) 

 

Power (kw) = (Air Flow) X (Air Density) X (Roof Temperature 

– House Temperature) 

 
The  following  graph  shows  the  expected  heat  gain  in  kilowatts  based  on  assumptions  that  the 
atmospheric pressure is normal at sea level (1013 mbar), air density is constant @ 1.24 kg/m3) 
and that flow rate is 200 l/s which is maximum speed of a single HVS2 fan. 
 

Relative Heat Contribution

-1.00

0.00

1.00

2.00

3.00

4.00

5.00

18

20

22

24

26

28

30

Roof Temperature

ki

lo 

w

at

ts

12

14

16

18

20

 

 
Each  coloured  line  on  the  graph  represents  various  house  temperatures  which  determines  the 
relative heating/cooling effect from the incoming air.  If the air temperature in the roof is the same 
as inside the house, then obviously there is zero heat gain.  If the roof temp is greater than the 
inside air then there is a gain. Conversely if the roof air is colder than inside the home then there 
is a heat loss. 
 
Graph examples: 

  If the house temperature is 16 degrees (yellow line) and the Roof Temp is 26 degrees, the 

heat gain is 2.5kw (2,500 watts). 

  If the house temperature is 20 degrees (purple line) and the Roof Temp is 26 degrees, the 

heat gain is 1.5kw (1,500 watts) 

  If the house temperature is 20 degrees (purple line) and the Roof Temp is 18 degrees, the 

heat loss is 0.5kw (500 watts) 

 
During condensation control mode (roof temp between 5 and 18), the fan speed is reduced which 
reduces the amount of heat loss to as little as 170 watts in the worst case scenario (outside temp 
of  3  degrees,  inside  temp  of  12  degrees  and  roof  temp  of  5  degrees).  Typical  night  time 
condensation  control  mode  of  say  8  degrees  outside,  12  degrees  in  the  roof  and  16  degrees 
inside would account for only 100 watts of heat loss (that of a light bulb). 
 

The  above  does  not  take  into  account  the  significant  energy  savings  resulting  from  the 
drying effect (displacement of moist humid air with dryer fresh air). 

Содержание "Warm N Dry" HVS1

Страница 1: ...What Is Condensation Control 3 What Is Heat Recovery Ventilation 3 Operating Principles 4 OPERATING GUIDELINES 5 General 5 Control Panel 6 Summer Months 7 Factory Default Settings 7 Other Settings 7...

Страница 2: ...logy Home Ventilation Solutions now manufactures its own systems built in Tasmania for Tasmanian conditions and sold by specialist retailers Your HVS Features Reduces condensation throughout the whole...

Страница 3: ...ng a typical day The sample was for the 10 5 08 and shows a minimum temp of 12 and a maximum of 28 degrees The actual outside minimum was just 10 8 and a maximum of just 17 on that day refer Appendix...

Страница 4: ...nto the home is required to banish condensation during winter The ventilation air supply positively pressurises the home causing stale air to be gently forced out through cracks under doors floor boar...

Страница 5: ...ufficient however if internal doors get closed extra outlets will be required The air from your Home Ventilation System is filtered for your protection The filter should to be replaced every 12 months...

Страница 6: ...speed dial controls the amount of air transferred during the ventilation mode which is the temperature range between SP1 and SP2 It can be manually varied between 30 and 100 of the fans air flow capa...

Страница 7: ...es If the condensation problem is very bad SP2 could be reduced to as low as 3 degrees but home heating would need to be increased If the condensation problem is only slight then SP2 could be set to a...

Страница 8: ...blems have the following performance guarantee If after 3 consecutive winter months the Customer is dissatisfied with the level of condensation control and the Customer has been adhering to all operat...

Страница 9: ...eck the filter f Do not use un flued gas heaters in the home g Ensure exhaust extraction fans are not dumping moisture into the roof space h Check for other sources of moisture that could effect the r...

Страница 10: ...Maximum Outlets HVS1 80 to 160 m 62 watts 45 135 l s 2 4 HVS2 120 to 240 m 80 watts 66 199 l s 2 6 HVS3 220 to 480 m 160 watts 132 398 l s 4 12 subject to change without notice Setting the Thermostat...

Страница 11: ...14 5 19 Mo 8 8 18 4 20 Tu 6 2 16 8 The following graph shows the roof space temperature at 108 Gormanston Road Moonah for the period 6 May 08 to 20 May 08 The blue line SP2 5 degrees and the red line...

Страница 12: ...ming air If the air temperature in the roof is the same as inside the house then obviously there is zero heat gain If the roof temp is greater than the inside air then there is a gain Conversely if th...

Отзывы: