17
COMBUSTION AND VENTILATION AIR (cont.)
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the roof surface with a listed
cap or listed roof assembly. Gas vents 12 inches in size or
smaller with listed caps shall be permitted to be terminated in
accordance with Figure 9, provided they are at least 8 feet
from a vertical wall or similar obstruction. All other gas vents
shall terminate not less than 2 feet above the highest point
where they pass through the roof and at least 2 feet higher
than any portion of a building within 10 feet.
2. A type B-1 gas vent shall terminate at least 5 feet in vertical
height above the highest connected equipment draft hood or
flue collar.
3. Must rise
1
/
4
” per foot away from the furnace on horizontal runs
and be supported with straps or hangers so it has no sags or
dips. Supports at 4 foot intervals and at all elbows are recom-
mended.
4. The vent connector must be mechanically fastened to the out-
let collar of the furnace with at least (2) sheet metal screws ex-
cept vent connectors that are B-1 material. These shall be
assembled in accordance with the manufacturer’s instructions.
See Figure 10.
5. Any angle greater than 45 degrees from the vertical is consid-
ered horizontal. The total horizontal distance of a vent plus the
horizontal vent connector serving draft-hood equipped appli-
ances shall not be greater than 75 percent of the vertical
height of the vent.
Single appliance venting of a fan assisted furnace into a tile-lined
masonry chimney is prohibited. The chimney must be lined with
either Type B vent or with a listed, single wall system. Reference
National Fuel Gas Code, ANSI Z223.1. See Figure 11 for typical
B-1 vent chase.
SPECIAL VENT SYSTEMS (SVS)
IMPORTANT:
It is THE FURNACE MANUFACTURER’s position
now that new installations of any HTPV pipe used in a category
III
vent application, including Selkirk’s Selvent™
II
HTPV prod-
uct, should cease immediately.
!
WARNING
DO NOT CONNECT THIS FURNACE TO A CHIMNEY USED
TO VENT A SOLID FUEL APPLIANCE (WOOD OR COAL).
VENTING WITH A SOLID FUEL APPLIANCE CAN LEAD TO
IMPROPER FUNCTIONING OF THE UNIT, AND DUE TO
SOOTING, THE POSSIBILITY OF FIRE RESULTING IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
VENT PIPE
FLUE PIPE
PRE-DRILL
ATTACHING
HOLES
FIGURE 17
ST-A1227-05
FIGURE 10
ATTACHING TO DRAFT INDUCER COLLAR
LISTED CAP
LISTED GAS VENT
ROOF PITCH = X/12
12
X
“H” - MINIMUM ALLOWABLE HEIGHT
FROM ROOF TO DISCHARGE OPENING
F
ROOF PITCH
“H” (MIN.) FT.
FLAT TO 6/12
1.0
OVER 6/12 TO 7/12
1.25
OVER 7/12 TO 8/12
1.5
OVER 8/12 TO 9/12
2.0
OVER 9/12 TO 10/12
2.5
OVER 10/12 TO 11/12 3.25
OVER 11/12 TO 12/12 4.0
OVER 12/12 TO 14/12 5.0
OVER 14/12 TO 16/12 6.0
OVER 16/12 TO 18/12 7.0
OVER 18/12 TO 20/12 7.5
OVER 20/12 TO 21/12 8.0
ST-A1220-24
FIGURE 9
TYPICAL VENTING WITH “B-1” VENT
ST-A1220-24