igfP-R3, R3P-0608

1

Refrigeration

Plumbing

waste outlet and P-tRaP

The waste outlet is located off the center of the case on 

one side allowing drip piping to be run lengthwise under 

the fixture. There are 3 drains in each fixture that can be 

easily located.

1-1/",  1"  and  3/4"  P-TRAPS  and  threaded  adapters 

are supplied with each fixture. The 3 P-TRAPS must be 

installed to prevent air leakage and insect entrance into 

the fixture.

note:   Pvc-dwv solvent cement is recommended. follow the 

manufacturer’s instructions.

installing condensate drain

Poorly  or  improperly  installed  condensate  drains  can 

seriously interfere with the operation of this refrigerator, and 

result in costly maintenance and product losses. Please 

follow the recommendations listed below when installing 

condensate drains to insure a proper installation:

1.   Never use pipe for condensate drains smaller 

than the nominal diameter of the pipe or P-TRAP 

supplied with the case.

.   When connecting condensate drains, the P-TRAP 

must be used as part of the condensate drain 

to prevent air leakage or insect entrance. Store 

plumbing system floor drains should be at least 14" 

off the center of the case to allow use of the P-TRAP 

pipe section. Never use two water seals in series in 

any one line. Double P-TRAPS in series will cause a 

lock and prevent draining.

3.   Always provide as much down hill slope ("fall") as 

possible; 1/8" per foot is the preferred minimum. 

PVC pipe, when used, must be supported to 

maintain the 1/8" pitch and to prevent warping.

4.   Avoid long runs of condensate drains. Long runs 

make it impossible to provide the "fall" necessary for 

good drainage.

5.   Provide a suitable air break between the flood rim of 

the floor drain and outlet of condensate drain. 1" is 

ideal.

6.   Prevent condensate drains from freezing:

a. Do not install condensate drains in contact with 

non-insulated suction lines. Suction lines should 

be insulated with a non - absorbent insulation 

material such as Armstrong's Armaflex.

b. Where condensate drains are located in dead 

air spaces (between refrigerators or between a 

refrigerator and a wall), provide means to prevent 

freezing. The water seal should be insulated to 

prevent condensation.

Refrigerant type

The  standard  refrigerant  will  be  R-  unless  otherwise 

specified on the customer order. Check the serial plate on 

the case for information.

Piping

The  refrigerant  line  outlets  are  located  under  the  case. 

Locate first the electrical box, the outlets are then on the 

same side of the case but at the opposite end. Insulate 

suction lines to prevent condensation drippage.

Refrigeration lines

Liquid 

Suction

3/8” O.D.

5/8” O.D. 

note:   the standard coil is piped at 

5

/

8

” (suction); however, 

the store tie-in may vary depending on the number of 

coils and the draw the case has. depending on the case 

setup, the connecting point in the store may be 

5

/

8

”, 

7

/

8

”, 

or 1

1

/

8

”. Refer to the particular case you are hooking up.

Refrigerant  lines  should  be  sized  as  shown  on  the 

refrigeration legend furnished by the store.
Install 

P-tRaPS

 (oil traps) at the base of all suction line 

vertical risers.

Pressure drop

 can rob the system of capacity. To keep the 

pressure drop to a minimum, keep refrigerant line run as 

short as possible, using the minimum number of elbows. 

Where elbows are required, use long radius elbows only.

control Settings

See  R3,  R3P  technical  data  sheet  for  the  appropriate 

settings for your merchandiser. Maintain these parameters 

to achieve near constant product temperatures. Product 

temperature should be measured first thing in the morning, 

after  having  been  refrigerated  overnight.  Defrost  times 

should be as follows: OFF CYCLE - Defrost times should 

be as directed in the R3, R3P technical data sheet. The 

number of defrosts per day and the duration of the defrost 

cycle may be adjusted to meet conditions present at your 

location.

access to tX valves and drain lines

Mechanical -

 Remove product from end of case. Remove 

product  racks.  Remove  refrigeration  and  drain  access 

panels (labeled). TX valve (mechanical only) and drain are 

located under each access panel at end of the case.

electronic - 

The Electronic Expansion valve master and 

slave cylinder(s) are located within the electrical access 

panel(s).

Содержание Specialty Products R3P

Страница 1: ...Refrigerated Service and or Prep with refrigerated self service front P N IGFP R3 R3P 0608 INSTALLATION OPERATION GUIDE CHINO R3 R3P Ref Service self service prep case Rev 0608 Installation Operation...

Страница 2: ...ains Information on R3 Refrigerated Service Top Self Service Front Case R3P Service Prep Top Refrigerated Self Service Front Case R3TO Service Top only for in counter installation Shipping Damage All...

Страница 3: ...tional Shelf R3P Service Prep Self Service Case Scale 1 2 12 3 8 18 10 20 5 8 13 1 2 50 3 8 19 3 8 6 36 3 8 13 1 2 50 3 8 50 1 4 40 1 2 52 1 8 20 5 8 2 0 7 8 10 5 8 Prep Top Area 19 3 8 12 6 12 8 R3 O...

Страница 4: ...fect of one continuous display A joint trim kit is supplied with each joint Leveling IMPORTANT IT IS IMPERATIVE THAT CASES BE LEVELED FROM FRONT TO BACK AND SIDE TO SIDE PRIOR TO JOINING A LEVEL CASE...

Страница 5: ...ten Join the top by using a joint bracket included in joint kit with 3 8 bolts Joint Trim After cases have been leveled and joined and refrigeration electrical and wasted piping work completed install...

Страница 6: ...easure 10 inches from top of the case Note Line up 6 inch mark with 10 inch mark Step 3 Use bracket center hole to align with cross mark Note Use pencil marker to mark hole pattern HOLE PATTERN Step 4...

Страница 7: ...ont d Step 6 Install upper support bracket Step 7 Mount wrap board on top of bracket using a spacer to have a gap between rear wall and board Step 8 screw bracket into wrap board screws provided 8 X 1...

Страница 8: ...bumper slide into the channel Step 3 Starting on one end while inserting the bumper push it up against the end cap to prevent the bumper from shrinking after installation when it gets cold Step 4 As y...

Страница 9: ...ositioned within the base grooves Roll vinyl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over the Rigid Ba...

Страница 10: ...length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over the Rigid Base 3 If necessary wipe clean with any household cleaning pr...

Страница 11: ...gs are positioned within the base grooves Roll vinyl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over the...

Страница 12: ...ins are located in dead air spaces between refrigerators or between a refrigerator and a wall provide means to prevent freezing The water seal should be insulated to prevent condensation Refrigerant T...

Страница 13: ...E Refer to label affixed to case to determine the actual configuration as checked in the TYPE INSTALLED boxes Electrical Circuit Identification Standard lighting for all refrigerated models will be fu...

Страница 14: ...pidly deteriorate 3 Maintain the display merchandisers temperature controls as outlined in the refrigerator section of this manual 4 Do not place any product into these refrigerators until all control...

Страница 15: ...nti fog capabilities This product also seals pores and provides a protective coating User Information Cont d CLEANING PRECAUTIONS When cleaning Do not use high pressure water hoses Do not introduce wa...

Страница 16: ...rams R3 Prep 4 W0180047 6 W0180048 8 W0180049 12 W0180051 R3 P 8 REM 8 W1800167 R3 P 4 REM WALMART 4 W1800172 R3 P 6 REM WALMART 6 W1800173 R3 Top Only Cold 4 W0180101 6 W0180102 8 W0180103 12 W018010...

Страница 17: ...load ratings removed fuse 8 29 07 JR 03 17 06 R3 CR3 CASES W0180047 R3 CR3 4 PREP CASES LIGHT SWITCH TIPPETTE 125 01 0311 L F28T5 48 125 03 1131 LIGHT CIRCUIT TAG ORANGE FAN CIRCUIT TAG BROWN BALLAST...

Страница 18: ...IGHT SWITCH TIPPETTE 125 01 0311 L LIGHT CIRCUIT TAG ORANGE FAN MOTOR CIRCUIT TAG BROWN BALLAST 125 01 3266 FULHAM LH3 120 L FP21 830 T5 36 125 03 1131 FP21 830 T5 36 125 03 1131 EVAP FAN MOTORS 4 4W...

Страница 19: ...LIGHT SWITCH TIPPETTE 125 01 0311 BALLAST 125 01 3266 FULHAM LH3 120 L L F28T5 48 125 03 1131 F28T5 48 125 03 1131 LIGHT CIRCUIT TAG ORANGE FAN CIRCUIT TAG BOTTOM BROWN M M M M EVAP FAN MOTORS 4 4W 29...

Страница 20: ...CASES LIGHT SWITCH TIPPETTE 125 01 0311 BALLAST 125 01 3266 FULHAM LH3 120 L L F28T5 48 125 03 1131 F28T5 48 125 03 1131 LIGHT CIRCUIT TAG ORANGE FAN MOTOR TAG BROWN M M M M M M EVAP FAN MOTORS 6 4W...

Страница 21: ...3178 CIRCUIT 3 W G BK LIGHT CIRCUIT 47A CIRCUIT 2 BLK 14 RED 14 WHT 14 BLACK 14 F28T5 48 125 03 1131 GRN 14 SENSOR 225 01 3228 F28T5 48 125 03 1131 FAN MOTOR 0 29 AMP 120VAC 4 0392457 M M M M SENSOR...

Страница 22: ...90 4910 Lic 644406 REVISIONS DESCRIPTION CHECKED BY BY FILE LOCATION JESSE RIOS PAGE OF 2 2 4 12 07 W1800167 R3 P 8REM 914276 LOADING 120 V L1 L2 L3 3 9 NOTE CASE MUST BE GROUNDED LOADING 208 V 240V L...

Страница 23: ...65A MOP 15A BUNDLE ORANGE LABELED LIGHT CIRCUIT L1 N L1 N BLACK 14 WHITE 14 BLACK 14 WHITE 14 WARMER 4ft 125 01 0767 TYCO THERMAL CONTROLS 10BTV1 CR 40 WATTS 0 33AMP 120V BUNDLE PURPLE LABELED HEATER...

Страница 24: ...N BLACK 14 WHITE 14 BLACK 14 WHITE 14 WARMER 6ft 125 01 0767 TYCO THERMAL CONTROLS 10BTV1 CR 60 WATTS 0 5AMP 120V BUNDLE PURPLE LABELED HEATER CIRCUIT LI N 120 VAC 1 50 60 Hz MCA 63A MOP 15A BOHN COIL...

Страница 25: ...1 0311 L F28T5 48 125 03 1131 T STAT 1 225 01 0707 SUCTION SOLENOID 1 225 01 3202 BUNDLE BLACK WHITE BUNDLE BROWN AXIAL EVAP FANS 0 16 AMP 11W 120VAC 2 125 01 2011 BALLAST 125 01 3266 FULHAM LH3 120 L...

Страница 26: ...0311 L T STAT 1 225 01 0707 SUCTION SOLENOID 1 225 01 3202 BUNDLE ORANGE BUNDLE WHITE BLACK M BUNDLE BROWN BALLAST 125 01 3266 FULHAM LH3 120 L FP21 830 T5 36 2 125 03 1131 120 VAC 60 Hz MCA 49A MOP 1...

Страница 27: ...11 BALLAST 125 01 3266 FULHAM LH3 120 L L F28T5 48 2 125 03 1131 T STAT 1 225 01 0707 SUCTION SOLENOID 1 225 01 3202 BUNDLE ORANGE BUNDLE WHITE BLACK BUNDLE BROWN M M M M 120 VAC 60 Hz MCA 65A MOP 15A...

Страница 28: ...AST 125 01 3266 FULHAM LH3 120 L L F28T5 48 125 03 1131 F28T5 48 125 03 1131 T STAT 1 225 01 0707 SUCTION SOLENOID 1 225 01 3202 BUNDLE ORANGE BUNDLE WHITE BLACK BUNDLE BROWN M M M M M M 120 VAC 60 Hz...

Страница 29: ...GON 8045 00 115 V 60 Hz 125 01 0710 CONDENSER FAN T STAT POWER SWITCH M M M BUNDLE YELLOW SAFETY SWITCH FLOAT SWITCH 120 VAC 60 Hz MCA 15 6A MOP 20A PLUG NEMA 5 15P L1 N BLACK 14 WHITE 14 FISHER EVAPO...

Страница 30: ...orm a complete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant acc...

Страница 31: ...warm product 2 Is the product loaded beyond the Safe Load Line markers 3 Are the return air ducts blocked 4 Are the entering air ducts blocked 5 Is a dumped display causing turbulent air flow and mix...

Страница 32: ...d store refrigerators are not food chillers nor can they reclaim quality lost through previous mishandling d Care must be taken when cross merchandising products to ensure that potentially hazardous v...

Страница 33: ..._______________________________ _______________ ___________________________________________________________________________________________________ _______________ ____________________________________...

Отзывы: