background image

IGSSB-SCSS / SCSS-SL-0108

2

/Chino

A publication of
Hussmann

®

 Chino

13770 Ramona Avenue • Chino, California 91710
(909) 628-8942 FAX
(909) 590-4910
(800) 395-9229

Keep this booklet with the case at all times for future reference.

THIS BOOKLET CONTAINS INFORMATION ON:

MODEL DESCRIPTIONS

All models are available in either 48”, 60” lengths.
SCSSSL - Non-refrigerated Summit Cake Self-Service
Bakery Case with 1, or 2 tier merchandising, and  rear
signage.
SCSSSL - Refrigerated Summit Cake Self-Service Bakery
Case with 1,or 2 tier merchandising, and rear signage.
Remote unit requires separate condenser unit connection.
Low Temperature Model (SCSSSL-RLL).
SCSSSL -Self-contained refrigerated Summit Cake Self-
Service Bakery Case with 1, or 2 tier merchandising, and
rear signage. Low Temperature Model (SCSSSL-S/CHL).

APPLICATION

These service-type merchandisers have been specifically
designed for bakery departments. The front glass provides
complete product visibility.
The  SCSSSL- non-refrigerated model, is designed to
display fresh bakery products that have fast turnover and
require no refrigeration. The SCSSSL- remote, and
SCSSSL- self-contained, refrigerated baker y
merchandisers are designed for use only in air conditioned
stores where temperature and humidity are maintained
at or below 75

°

F dry bulb temperature and 55% relative

humidity.

SHIPPING DAMAGE

All equipment should be thoroughly examined for ship-
ping damage before and during unloading.
This equipment has been carefully inspected at our fac-
tory and the carrier has assumed responsibility for safe
arrival. If damaged, either apparent or concealed, claim must
be made to the carrier.

APPARENT LOSS OR DAMAGE

If there is an 

obvious loss or damage

, it must be noted on

the freight bill or express receipt and signed by the carrier’s
agent; otherwise, carrier may refuse claim. The carrier will
supply necessary claim forms.

CONCEALED LOSS OR DAMAGE

When loss or damage

 is not apparent until after equipment

is uncrated

, a claim for concealed damage is made. Make

request in writing to carrier for inspection within 15 days,
and retain all packaging. The carrier will supply inspection

General Instructions

Table of Contents

General Instructions ................................................. 2
Cut & Plan Views ....................................................... 4
Installation ................................................................. 5

LEVELING .............................................................................................................. 5

Plumbing .................................................................... 6

WASTE OUTLET AND P-TRAP .............................................................................. 6
JOINT TRIM ........................................................................................................... 6

Refrigeration ............................................................. 7

T-STAT LOCATION .................................................................................................. 8
Condensing Unit Installation Requirements ....................................................... 8

Electrical .................................................................... 9

WIRING COLOR CODE ......................................................................................... 9
ASHRAE COLOR CODE .......................................................................................... 9

User Information ...................................................... 12

STOCKING .............................................................................................................. 12
CASE CLEANING .................................................................................................... 12
NON-GLARE GLASS ............................................................................................... 13
PLEXIGLASS & ACRYLIC CARE .............................................................................. 13

Maintenance .............................................................. 14

ELECTRICAL PRECAUTIONS ................................................................................... 14

14

REPLACING FLUORESCENT LAMPS ....................................................................... 14

Electrical and Refrigeration Specifications ............ 14

TIPS & TROUBLESHOOTING ................................................................................. 14

Electrical Schematics ............................................... 15
Appendices ................................................................ 19

APPENDIX A. – Temperature Guidelines ............................................................ 19
APPENDIX B. – Application Recommendations .................................................. 19
APPENDIX C. – Field Recommendations - ......................................................... 19
APPENDIX D. – Recommendations to user - .................................................... 20

Содержание SCSS

Страница 1: ... Chino SCSS SCSS SL SERVICE BAKERY REV 0108 Installation Operation Manual SCSS SCSS SL SERVICE BAKERY P N IGSSB SCSS SCSS SL 0108 INSTALLATION OPERATION GUIDE ...

Страница 2: ...PPING DAMAGE All equipment should be thoroughly examined for ship ping damage before and during unloading This equipment has been carefully inspected at our fac tory and the carrier has assumed responsibility for safe arrival If damaged either apparent or concealed claim must be made to the carrier APPARENT LOSS OR DAMAGE If there is an obvious loss or damage it must be noted on the freight bill o...

Страница 3: ...n inspection Hussmann Chino will acknowledge shortages within ten days from receipt of equipment HUSSMANN CHINO PRODUCT CONTROL The serial number and shipping date of all equipment has been recorded in Hussmann s files for warranty and re placement part purposes All correspondence pertaining to warranty or parts ordering must include the serial num ber of each piece of equipment involved in order ...

Страница 4: ...S Plan view Scale 1 2 Elec Stub Up 9 12 1 2 24 1 2 35 1 2 6 1 2 44 1 2 17 1 2 Drain Location 10 48 Variable Front Of Case SCSS SL Summit Cake Self Service Bakery Case Slim Line Remote Self Contained Scale 1 2 12 14 1 4 4 3 4 14 14 3 4 Low Temp Ht 21 1 4 S C Height 15 3 4 Remote Height 5 1 2 Med Temp Height 7 3 4 40 3 4 S C Height 9 3 4 25 1 2 11 3 4 15 1 4 35 1 4 Remote Height 38 Refrig Stub Up 24...

Страница 5: ...ined prior to shipment to insure the closest possible fit when cases are joined in the field When joining use a carpenters level and shim legs accordingly Case must be raised correctly under legs where support is best to prevent damage to case 1 Check level of floor where cases are to be set Determine the highest point of the floor cases will be set off this point 2 Set first case and adjust legs ...

Страница 6: ...draining 3 Always provide as much down hill slope fall as possible 1 8 per foot is the preferred minimum PVC pipe when used must be supported to main tain the 1 8 pitch and to prevent warping 4 Avoid long runs of condensate drains Long runs make it impossible to provide the fall necessary for good drainage 5 Provide a suitable air break between the flood rim of the floor drain and outlet of conden...

Страница 7: ...t coil outlet and in the discharge air Some supermarkets require a 4th sensor in the return air Case controllers will be located in the electrical raceway or under the case THERMOSTATIC EXPANSION VALVE LOCATION This device is located on the same side as the refrigera tion stub A Sporlan balanced port expansion valve model is furnished as standard equipment unless otherwise speci fied by customer E...

Страница 8: ...0V 60 Hz electrical supply PIPING For merchandisers with electric defrost the suction and liquid lines should be clamped or taped together and insulated for a minimum of 30 feet For models with KOOLGAS defrost suction and liquid lines should not contact each other and should be insulated separately for a minimum of 30 feet With either type defrost additional insulation for the balance of the liqui...

Страница 9: ... the case WIRING SERIAL PLATE AMPERAGE Field Wiring must be sized for component amperes stamped on the serial plate Actual ampere draw may be less than specified Field wiring from the refrigeration con trol panel to the merchandisers is required for refrigera tion thermostats Most component amperes are listed in the Case Specs section but always check the serial plate ASHRAE COLOR CODE NOTE All ot...

Страница 10: ...ll parameter settings factory Normal operation Normal operation Normal operation Alarm relay not Alarm Room temp Room temp Set value Change Change Change Set value Room temp Room temp Power off Power on Room temp Room temp Room temp Room temp Room temp Alarm code Fault code Alarm code Fault code Room temp Room temp Defrost operation Defrost sensor temp What to do Initial controller Read or change ...

Страница 11: ...temp setting differential 2 A01 0 K 50 K 5 K Lower deviation below temp setting 2 A02 0 K 50 K 5 K Temperature alarm delay A03 0 min 90 min 30 min Door alarm delay A04 0 min 60 min 30 min Compressor Min ON time c01 0 min 15 min 0 min Min OFF time c02 0 min 15 min 0 min Cut in frequency on sensor fault 3 c03 0 100 0 Defrost Defrost method EL GAS d01 EL Defrost stop temperature d02 0o C 25o C 6o C I...

Страница 12: ...e product to extend beyond the recommended load limit Air dis charge and return air flue must be unob structed at all times to provide proper refrig eration 6 There are vents located at the base of the front of the glass just above the front rail These vents supply a continuous gentle flow of air across the front glass which inhibits condensation Do not place any signs or other restrictive objects...

Страница 13: ... may shatter and cause serious injury Allow glass surfaces to warm first NON GLARE GLASS The high optical clarity of this glass is possible due to spe cial coatings on the glass surface itself To preserve this coating and the optical clarity keep the glass clean Windex or Glass Plus are the only solutions recom mended to be used to clean the non glare glass The dam age to the glass from improper c...

Страница 14: ...ype Fan Blade Defrosts Electrical Load Amps 115 VAC Condensing Unit Data Btu Hr Temperatures F Speed Settings Size in Evap Motors per day Evap Fans Case Case Defrost Glass Set PSI Size Voltage Ampacity Length Ft Total Evap Prod Disch CFM F pitch Fans Qty Length Qty Fans Warmer Lights Heater Heater Out In HP VAC SCSS M MediumTemperature 4 650 2 600 20 40 30 200 Optional Forced Air 4 Axial 2 30 2 0 ...

Страница 15: ...Lic 644406 Revisions No Description Checked By By File Location Boris Kasrel BJK Sheet of W8000001mnl H WiringSchematics NewWiringDiagrams BOM Prod Refrigerated Medium Temp Self Service Desplay SCSS M Remote Off Cycle Defrost Wiring Diagram 00 00 00 1 1 115V M M M M Anti Sweat Heater Evaporator Fans Glass Heater J BOX Temp Sensor to Temp Defrost Controller 115V 1Ph 60Hz 2 5A ...

Страница 16: ...tics In Work 495 01 880 03 29 01 W8100001mnl Refrigerated Low Temp Self Service Display SCSS L E Remote Electrical Defrost Wiring Diagram 1 1 115V 208 230V M M M M Klixon 20420L15 013 302 L40 1 5 Q00VA Anti Sweat Htr 85W 115V Htr Shut Off Evaporator Glass Htr 60W 115V 2 208 230V Finned Defrost Htr Temp Sensor to Temp Defrost Controller J Box SCSS L KG Remote Kool Gas Defrost Legend controls lines ...

Страница 17: ...0002mnl Refrigerated Low Temp Self Service Display SCSS L KG Remote Kool Gas Defrost Wiring Diagram 1 1 115V 208 230V M M M M Klixon 600 22 0010 20420l28 229 89 L20 1 5 R98A Klixon 20420L15 013 302 L40 1 5 Q00VA Anti Sweat Htr 85W 115V Fans Shut Off Htr Shut Off Evaporator Glass Htr 60W 115V 208 230V Finned Defrost Htr Temp Sensor to Temp Defrost Controller J Box SCSS L KG Remote Kool Gas Defrost ...

Страница 18: ...5V 208 230V M M M M Anti Sweat Htr 85W 115V Evaporator Glass Htr 60W 115V 2 208 230V Finned Defrost Htr J Box SCSS L E S C Low Temp Self Contained ElectricalDefrost Legend controls lines 12 orange 12 black 12 orange 12 black 12 black 12 white 12 green EKC 201 12V 12 14 13 15 16 17 8 9 10 11 2 4 1 3 7 5 6 Temp Probe Defrost Termination Temp Probe Evap Temp High Low Pressure Safety 208 230 1Ph Conde...

Страница 19: ...stallation of thesystemwhichdispensescondensatewastethrough an air gap into the building indirect waste system 1 4 The installer should perform a complete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant according to manufacturer s recommendations b Observation of ou...

Страница 20: ...ights or other high intensity lighting directed onto the product 7 Are there unusual draft conditions from heating air conditioning ducts open doors etc 8 Is there exposure to direct sunlight 9 Are display signs blocking or diverting airflow 10 Are the coils of the refrigerator iced up 11 Is the store ambient over 75 F 55 RH as set forth in ASHRAE Standard 72 and ASHRAE Standard 117 12 Are the she...

Страница 21: ...on refriger ated areas e Display and storage equipment doors should be kept closed during periods of inactivity f Minimize the transfer time of perishables from storage to display g Keepmeatunderrefrigerationinmeatcuttingand processing area except for the few moments it is being handled in processing When a cut or tray of meat is not to be worked on immediately the procedure should call for return...

Страница 22: ...IGSSB SCSS SCSS SL 0108 22 ...

Страница 23: ...under this warranty shall be limited to a period not to exceed five years from date of factory shipment On Hussmann refrigeration systems an additional 4 year extended warranty for the motor compressor assembly is available but must be purchased prior to shipment to be in effect Hussmann reserves the right to inspect the job site installation and reason for failure The motor compressor warranties ...

Страница 24: ...r particular unit They can be found on a small metal plate on the unit Please note them below for future reference MODEL SERIAL NUMBER Chino Additional copies of thispublication may be obtained by contacting Hussmann Chino 13770 Ramona Avenue Chino California 91710 909 628 8942 FAX 909 590 4910 800 395 9229 Service Record Last service date By ...

Отзывы:

Похожие инструкции для SCSS