installation

location

The  refrigerated  merchandisers  have  been  designed 

for use only in air conditioned stores where temperature 

and   humidity are maintained at or below 75°F and 55% 

relative humidity. DO NOT allow air conditioning, electric 

fans, ovens, open doors or windows (etc.), to create air 

currents around the merchandiser, as this will impair its 

correct operation.
Product  temperature  should  always  be  maintained  at  a 

constant and proper temperature. This means that from the 

time the product is received, through storage, preparation 

and  display,  the  temperature  of  the  product  must  be 

controlled to maximize life of the product.

uncrating the Stand

Place  the  fixture  as  close  to  its  permanent  position  as 

possible . Remove the top of the crate. Detach the walls 

from each other and remove from the skid. Unbolt the case 

from the skid. The fixture can now be lifted off the crate 

skid. 

lift only at base of stand!

exterior loading

These models have not been designed to support excessive 

external loading. 

do not use the lower surfaces, glass, 

or shelves as a stepping ladder. do not stand in lower 

cases to gain access to the upper portion of the case. 

do not stand on any opening in the side panels.

 Failure 

to observe these warnings could result damage to the case 

and serious personal injury.

leveling

iMPoRtant! it is imperative that cases be leveled from 

front to back and side to side. a level case is necessary 

to  insure  proper  operation,  water  drainage,  glass 

alignment,  and  operation  of  the  hinges  supporting 

the glass. leveling the case correctly will solve most 

hinge operation problems.

NOTE:   A. To avoid removing concrete flooring, begin lineup 

leveling from the highest point of the store floor.

 

B. When wedges are involved in a lineup, set them first.

All  cases  were  leveled  and  joined  prior  to  shipment  to 

insure the closest possible fit when cases are joined in the 

field. When joining, use a carpenters level and shim legs 

accordingly. 

case must be raised correctly, under legs 

where support is best, to prevent damage to case.

1.  Check level of floor where cases are to be set. 

Determine the highest point of the floor; cases will 

be set off this point.

.   Level and set the case. Case must be raised under 

legs where support is best to prevent damage to 

case. Internal bracing may be removed at this time.

It is the contractor's responsibility to install

case(s) according to local construction and

health codes.

Plumbing

Self contained cases

MZ3 self-contained cases do not require that a condensate 

drain  be  connected  because  all  of  the  condensate  is 

contained by the condensate pan. However it is required 

that the condensate pan be cleaned on a regular basis. 

Additionally, the condensing unit should be cleaned at the 

same  time  using  a  light,  non-abrasive  brush  to  remove 

accumulated dust. If a filter is installed, it should be cleaned 

at this time as well.

installing condensate drain (When applicable)

Poorly  or  improperly  installed  condensate  drains  can 

seriously interfere with the operation of this refrigerator, and 

result in costly maintenance and product losses. Please 

follow the recommendations listed below when installing 

condensate drains to insure a proper installation:

1 .  Never use pipe for condensate drains smaller 

than the nominal diameter of the pipe or P-TRAP 

supplied with the case.

 .  When connecting condensate drains, the P-TRAP 

must be used as par t of the condensate drain 

to prevent air leakage or insect entrance. Store 

plumbing system floor drains should be at least 14" 

off the center of the case to allow use of the P-TRAP 

pipe section. Never use two water seals in series in 

any one line . Double P-TRAPS in series will cause 

a lock and prevent draining.

3 .  Always provide as much down hill slope (“fall”) as 

possible; 1/8" per foot is the preferred minimum. 

PVC pipe, when used, must be supported to 

maintain the 1/8" pitch and to prevent warping.

4 .  Avoid long runs of condensate drains. Long runs 

make it impossible to provide the “fall” necessary for 

good drainage.

5 .  Provide a suitable air break between the flood rim of 

the floor drain and outlet of condensate drain. 1" is 

ideal.

Содержание MZ3-S

Страница 1: ...S Multi zone Refrigerated Self Service Self Contained P N IGSS MZ3 S 0909 INSTALLATION OPERATION GUIDE CHINO MZ3 S MULTI ZONE REFRIGERATED SELF SERVICE SELF CONTAINED Rev 0909 Installation Operation Manual ...

Страница 2: ...ely and request an inspection Hussmann Chino will acknowledge shortages within ten days from receipt of equipment HUSSMANN CHINO PRODUCT CONTROL The serial number and shipping date of all equipment has been recorded in Hussmann s files for warranty and replacement part purposes All correspondence pertaining to warranty or parts ordering must include the serial number of each piece of equipment inv...

Страница 3: ...71 6 20 1 4 18 1 4 16 1 4 37 1 4 30 7 8 27 5 8 19 3 4 10 7 8 9 3 8 9 3 8 1 5 8 1 7 8 1 7 8 1 5 8 50 3 8 47 1 4 37 1 4 6 ELECTRICAL CONNECTION 2 POWER CORDS 1 NEMA 5 15P 2 NEMA L5 20P MZ3 4S PLAN VIEW RCD FMSS LT Condensing Unit MZ3 SELF SERVICE MERCHANDISER ...

Страница 4: ...Case must be raised correctly under legs where support is best to prevent damage to case 1 Check level of floor where cases are to be set Determine the highest point of the floor cases will be set off this point 2 Level and set the case Case must be raised under legs where support is best to prevent damage to case Internal bracing may be removed at this time It is the contractor s responsibility t...

Страница 5: ...r location Control Settings self Contained All functions are controlled by Omni Stat Controllers See MZ3 S Technical Data Sheet for proper temperature and defrost settings Access to TX Valves and Drain Lines MECHANICAL Remove product from end of case Remove product racks Remove refrigeration and drain access panels labeled TX valve mechanical only and drain are located under each access panel at e...

Страница 6: ...rol temp Btu hr ft Parallel 400 Conventional 460 Low Temp Discharge Air F 10 Evaporator F 20 Note Not recommended to control temp by regulating coil temp allow T STAT to cycle and control temp Btu hr ft Parallel 600 Conventional 690 For all refrigeration equipment other than Hussmann use conventional Btu values Defrost Data Frequency Hrs 8 OFFTIME Temp Term F 54 Failsafe Minutes 30 ELECTRIC or GAS...

Страница 7: ...both cords before moving or servicing this equipment Attachment Plugs This unit contains two power supply cords Each cord is a different type Connect each plug to a single outlet circuit The first attachment plug is a NEMA 5 15P type plug with a 15 amp rating A 15 amp line is required for the NEMA 5 15P plug The second is a NEMA L5 20P type plug with a 20 amp rating A 20 amp line is require for th...

Страница 8: ...t dehydration Recommended Omni Stat Temperature Control Settings RCD 26 FMSS LT 15 See Case Specifications for Details 2 Temperature control is adjusted by the Omni Stat Temperature Controller Case Cleaning Long life and satisfactory performance of any equipment are dependent upon the care given to it To insure long life proper sanitation and minimum maintenance costs the refrigerator should be th...

Страница 9: ...t in damage to equipment serious personal injury This includes but not limited to Fans Heaters Thermostats and Lights Replacing Fluorescent Lamps Fluorescent lamps are furnished with moisture resistant lamp holders shields and end caps Whenever a florescent lamp is replaced be certain to reinstall the lamp shield and end caps over the lamp The lamps supplied are single slim line or bi pin type wit...

Страница 10: ...t safe and use a soft cloth or plastic scouring pad 3 Use Alkaline Alkaline Chlorinated or Non chloride Containing Cleaners While many traditional cleaners are loaded with chlorides the industry is providing an ever increasing choice of non chloride cleaners If you are not sure of your cleaner s chloride content contact your cleaner supplier If they tell you that your present cleaner contains chlo...

Страница 11: ...15V 60 Hz 952892 125 01 2304 AIR TEMP DEFROST TEMP 125 01 2301A MAX 16 FEET N GROUND FAN COMP 1 DEFROST SOLENOID 225 01 6004 225 01 6005 M M PRESSURE SAFETY CONDENSING UNIT C R BLACK 14 WHITE 14 LOWER HOT GAS DEFROST SECTION CONDUCTIVE GLASS HEATER 10 W FT 120VAC 40W 33A 150 01 7850 WARMER 4ft 125 01 0767 10BTV1 CR 40 WATTS 0 33AMP 120V BLACK 14 L1 N OMNI STAT PN 952896 120VAC POWER SUPPLY 115Vac ...

Страница 12: ...YELLOW DM10W 1D 1000W 120 VAC 8 33A 125 01 0758 SAFETY SWITCH FLOAT SWITCH PLUG NEMA 5 15P G BLACK 14 WHITE 14 DUPLEX 125 01 0096 CIRCUIT 2 PLUG NEMA 5 15P 125 01 0986 CIRCUIT 1 F28T5 48 125 03 1132 BALLAST 125 01 3266 FULHAM LH3 120 L TOGGLE SWITCH 125 01 0307 BALLAST 125 01 3266 FULHAM LH3 120 L LIGHT CIRCUIT 1 56A 168W BALLAST 125 01 3266 FULHAM LH3 120 L F28T5 48 125 03 1132 F28T5 48 125 03 11...

Страница 13: ...v 0 F v 10 F v 30 F v 110 F v 90F 0 F v 106 F v 80 F v 80 F v 80 F v 2000 BTU h 15 F v 2000 BTU h 20 F v ZONE 1 ZONE 2 Condenser Heat Exchanger Compressor Evaporator Evaporator Check Valve TXV TXV 4 way valve Accumulator Receiver EPR Liquid Stop Check Valve Check Valve ...

Страница 14: ...ete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant according to Hussmann recommendations b Observation of outside influences such as drafts radiant heating from the ceiling and from lamps Such influence should be properly corrected or compensated for c At the same ...

Страница 15: ...Are spotlights or other high intensity lighting directed onto the product 7 Are there unusual draft conditions from heating air conditioning ducts open doors etc 8 Is there exposure to direct sunlight 9 Are display signs blocking or diverting airflow 10 Are the coils of the refrigerator iced up 11 Is the store ambient over 75 F 55 RH as set forth in ASHRAE Standard 72 and ASHRAE Standard 117 12 Ar...

Страница 16: ...Care must be taken when cross merchandising products to ensure that potentially hazardous vegetable products are not placed in non refrigerated areas e Display and storage equipment doors should be kept closed during periods of inactivity f Minimize the transfer time of perishables from storage to display g Keep meat under refrigeration in meat cutting and processing area except for the few moment...

Страница 17: ..._________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ __...

Отзывы: