MK/MV – Medium Profile Series Unit Coolers (E206993_M)
17
Table 7 MV LOW TEMPERATURE/HIGH VELOCITY - ELECTRIC DEFROST
MODEL
CFM
STANDARD
CIRCUITS
NOZZLE
R404A
NOZZLE
R407A
NOZZLE
R448A
MV14E-73
4790
5
L-1
L-1
L-1-1/2
MV14E-100
4300
6
L-1-1/2
L-1-1/2
L-2
MV14E-128
4130
8
L-2
L-2
L-2-1/2
MV24E-146
9580
10
J-2-1/2
J-2
J-2-1/2
MV24E-200
8600
10
J-3
J-2-1/2
J-3
MV24E-256
8260
13
J-4
J-3
J-4
MV34E-300
12900
15
G-5
G-4
G-5
MV34E-383
12390
20
G-8
G-5
G-6
MV44E-512
16520
20
G-12
G-6
G-8
MV16E-93
4405
5
L-1-1/2
L-1-1/2
L-2
MV16E-126
3955
6
L-2
L-1-1/2
L-2
MV16E-155
3800
8
L-2-1/2
L-2
L-2-1/2
MV26E-186
8810
10
J-3
J-2-1/2
J-3
MV26E-252
7910
10
J-5
J-3
J-4
MV26E-310
7600
13
J-6
J-4
J-5
MV36E-378
11865
15
G-8
G-5
G-6
MV36E-465
11400
20
G-10
G-6
G-8
MV46E-620
15200
20
G-12
G-10
G-12
*Consult factory.
Note: Low temperature distributor nozzle selections are based on -20
°
F suction temperature, 10
°
F T.D.
and 85
°
F liquid temperature.
4.6
EXPANSION VALVE
Before mounting the unit, install the expansion valve and connect the equalizer tube. The expansion
valve should be installed directly to the distributor body or as close as possible with no elbows or bends.
Locate the expansion valve bulb on a horizontal length of suction line as close to the suction header as
possible. Position the bulb in a 3, 4, 8, or 9 o’clock position (do not position on the bottom side of the
pipe). Clamp the bulb down flush and tightly against the pipe and insulate. Never locate the bulb in a
trap or downstream from a trap.
Expansion valves are adjusted at the factory prior to shipment. The setting will be correct for many
applications, but in other applications adjustments may be needed. It is important that the operation of
the expansion valve be checked after the system has balanced out at the desired room temperature. If
the coil is being starved, it is necessary to reduce the superheat setting of the valve by turning the
adjusting stem counterclockwise. If the superheat is too low, it is necessary to increase the superheat
setting of the valve by turning the adjusting stem clockwise. It is recommended that for a 10
°
F to 12
°
F
T.D. system, the valve should be adjusted to maintain 5
°
F to 6
°
F superheat.
Содержание KRACK MK Series
Страница 1: ...MK MV Medium Profile Series Unit Coolers E206993_J Part Number E206993_M...
Страница 38: ...MK MV Medium Profile Series Unit Coolers E206993_M 35 Figure 22 Air Defrost Controller Wire Diagram...
Страница 39: ...MK MV Medium Profile Series Unit Coolers E206993_M 36 Figure 23 Air Defrost Slave Power Diagram...
Страница 42: ...MK MV Medium Profile Series Unit Coolers E206993_M 39 Figure 26 Electric Defrost Controller Wiring Diagram...
Страница 70: ...MK MV Medium Profile Series Unit Coolers E206993_M 67 Part Number E206993_M...