MK/MV – Medium Profile Series Unit Coolers (E206993_M)
21
5
ELECTRICAL
5.1
FIELD WIRING
WARNING: All power supply to the unit must be shut off before opening any compartments, cleaning
or performing maintenance.
Field wiring should comply with NEC and local codes. The power supply voltage, phase, and frequency
must match what is shown on the unit cooler data plate.
The field-wiring compartment is constructed as part of the unit cooler enclosure. The wiring diagram for
each unit is located on the inside of the electrical panel door. Wiring connections are made at the
terminal block(s) provided inside the unit on the end opposite the refrigerant connections. The unit
must be grounded. Refer to tables 9, 10, 11, and 12 for unit amps.
Special consideration must be taken when wiring single-phase fan motors and defrost heaters. If the
total amp draw of the motors or heaters exceed the amp rating of the fan delay or heater safety switch
then a contactor must be installed.
For units using Carbon Dioxide (R744) the defrost termination thermostat is to be located on the
topmost inlet tube from the inlet header as shown in Figure 8.
5.2
ELECTRICAL DATA
Table 11 MK MOTOR AMPS – 1/4 HP MOTOR
FANS
115/60/1
230/60/1
230/60/3
460/60/1
460/60/3
1 Fan
3.8
1.9
N/A
0.9
N/A
2 Fan
7.6
3.8
3.3
1.8
1.6
3 Fan
11.4
5.7
3.3
2.7
1.6
4 Fan
15.2
7.6
5.0
3.6
2.4
Table 12 MV MOTOR AMPS – 1/3 HP MOTOR
FANS
115/60/1
230/60/1
230/60/3
460/60/1
460/60/3
1 Fan
4.3
2.3
N/A
1.1
N/A
2 Fan
8.6
4.6
4.0
2.2
1.9
3 Fan
12.9
6.9
4.0
3.3
1.9
4 Fan
17.2
9.2
6.0
4.4
2.9
*Total 24 amps wired in two circuits.
Table 13 MK & MV EC AMPS – 1/3 HP MOTOR
FANS
115/60/1 230/60/1
1 Fan
4.5
2.6
2 Fan
9
5.2
3 Fan
13.5
7.8
4 Fan
18
10.4
Содержание KRACK MK Series
Страница 1: ...MK MV Medium Profile Series Unit Coolers E206993_J Part Number E206993_M...
Страница 38: ...MK MV Medium Profile Series Unit Coolers E206993_M 35 Figure 22 Air Defrost Controller Wire Diagram...
Страница 39: ...MK MV Medium Profile Series Unit Coolers E206993_M 36 Figure 23 Air Defrost Slave Power Diagram...
Страница 42: ...MK MV Medium Profile Series Unit Coolers E206993_M 39 Figure 26 Electric Defrost Controller Wiring Diagram...
Страница 70: ...MK MV Medium Profile Series Unit Coolers E206993_M 67 Part Number E206993_M...