Discharge the refrigerant-nitrogen 
mixture, allowing it to blow from the 
system as rapidly as possible, into an 
empty cylinder.  Be sure that all ser-
vice valves and solenoid valves are 
open to allow all of the mixture to be 
discharged. 

 

 

Connect a deep-drain vacuum pump 
to both the high and low side of the 
system.  Pull a vacuum on the system 
to at least 1500 microns. 

 

 

Break the vacuum by adding refriger-
ant into the system until the pressure 
is above 0 psig.  Always charge the re-
frigerant line into the system through 
a new drier in the charging manifold 
line.  A 16 cubic inch drier is sufficient 
for this purpose. 

 

 

Repeat steps 2 and 3 two more times, 
the third time evacuating the system 
to 500 microns. 

 
REMOTE CONDENSING UNIT  -  
 
 

The remote condensing unit is con-

structed of weather resistant G-90 galva-
nized steel for durability.  It includes the 
compressor, condenser, head pressure by-
pass valve, receiver (insulated), crankcase 
heater, drier, sight glass, condenser fan 
motors, fan delay thermostat, dual  pres-
sure control, solenoid valve, electrical 
box, and quick connects (optional). 
 
COMPRESSOR –  
 
 

The compressor is mounted on  

semi-rigid, rubber pads.  There are no 
mounting springs so the compressor is es-
sence becomes solid mounted.  DO NOT 
LOOSEN THE MOUNTING BOLTS ON 
THE COMPRESSOR. 
 
FAN DELAY THERMOSTAT –  
 
 

The fan delay thermostat is con-

nected to the left hand  fan motor (as you 
face the unit from the electrical box side) 
and will leave this fan off at ambients be-
low 65ºF to insure proper condensing tem-
peratures. 
 
HEAD PRESSURE BY-PASS VALVE –  
 
 

The head pressure by-pass valve is 

a pre-set, non-adjustable type.  Its function 
is to divert the refrigerant to the receiver 
when the head pressure falls below the set-
ting so that proper head pressure is main-
tained in the system and liquid is feeding 
the thermostatic expansion valve. 
 
CRANKCASE HEATER –  
 
 

The crankcase heater is located be-

low the compressor on semi-hermetic mod-
els  and wrapped around on hermetic mod-
els.  The heater is on at all times. 
 
CRANKCASE PRESSURE REGULA-
TOR –  
 
 

The remote units designed for the 

HGL-1-T/B and HGL-2-T/B employ a 
crankcase pressure regulator in the suction 
line.  The CPR is set for 10 psi on the  re-
mote unit  for both 1 and 2 door.  The pur-
pose of the valve is to maintain a low suc-
tion pressure on start-up so that the  
 

 

 
Page  13 

Содержание HGL-1BS

Страница 1: ...GL 1 2 3 BOTTOM TOP MOUNT REMOTES P N OII HGL Remotes January 2006 First Call for help US and Canada 1 800 922 1919 Soporte Tècnico y Asistencia Mèxico 01 800 522 1900 For a Service Network Locator and other Information visit us at www hussmann com select Worldwide Locations ...

Страница 2: ... Cleaning Routine Maintenance Operation and Maintenance 8 Power Switches 8 Temperature Control 8 Thermometer 9 Electrical Enclosure 9 Defrost Time Clock 10 Defrost Heater Thermostat 10 Defrost Heater Replacement 10 Lighting Door Switches 11 Door and Frame Heaters 11 Expansion Valve Adjustment 11 Alarm Thermostat Heater Delay 11 Refrigeration Leak Testing and Evacuation 12 Remote Condensing Unit an...

Страница 3: ...ration Line Sets 14 Pumpdown System on the Remote Unit 14 Setting up the Pumpdown System 15 Trouble Shooting Charts 16 19 Electrical Components List 19 Warranty and Parts Information 20 Ordering Replacement Parts 20 Warranty Parts Procedure 20 Compressor Replacement Procedure 21 ...

Страница 4: ...HGL only Is timer set for correct time of day Fail safe at 40 minutes de frost pins at 10 p m and 6 a m HGL only Are electrical connections tight and tubing positioned to prevent rubbing Is drain hose in water pan and trapped Does the condenser fan blade s turn freely Is the temperature control set per the following specifications Control Set At Cabinet Temperature HGL 18 13 off 9 on HGM HGS 29 to...

Страница 5: ...skid provides protection for both case and floor The skid is removed by raising one end of the case approximately six inches BLOCK SECURELY and remove the two skid bolts on the raised end The procedure is repeated on the opposite end When the skid bolts are removed the case may be slid off the skid LEG INSTALLATION Top Mounts Only After the case is near its final loca tion and the skid has been re...

Страница 6: ...proper airflow in the cabinet Behind the shelves are wire flue spacers which also allow for proper airflow All shelves and flue spac ers are white epoxy coated for durability and ease of cleaning Shelves should be adjusted to desired operating height When loading product into the cabinet care should be taken not to load product so that it touches the evaporator coil cover also do not extend produc...

Страница 7: ...he clock HGL cabinets are factory set for 2 defrost periods in 24 hours 6 a m and 10 p m Check the cabinet thoroughly for loose nuts and bolts and electrical connections Inspect the refrigera tion lines for any visible damage or chafing Replace the electrical box cover Start the cabinet and allow to pull down to operating temperature be fore loading BTU CAPACITIES RATING TEMP ºF BTU HR EVAP COND A...

Страница 8: ...PERATION MAINTENANCE behind the top decorative panel top mounts The switch will shut off all power TEMPERATURE CONTROL The electronic temperature con trol is located in the electrical box The temperature control does not have an OFF position Adjustments may be made by turning the knob on the face of the dial Turning it clockwise will give warmer temperatures while counter clockwise will give colde...

Страница 9: ...s making a decision on a product After the door is closed it will take some time for the thermometer to pull back down to the case temperature The ther mometer and temperature control sense discharge air temperature which is 5 10º colder than the case temperature ELECTRICAL ENCLOSURE The electrical enclosure contains the defrost time clock and temperature control For servicing convenience access i...

Страница 10: ...t should fail the timer is equipped with a failsafe set at 40 minutes that will allow defrost to termi nate on time DEFROST HEATER THERMOSTAT The defrost heater thermostat is clamped to the evaporator outlet tube It is a bi metal thermostat that is tied in se ries with the evaporator fans for a delay and with defrost time clock solenoid to end defrost when the temperature has been satisfied The ev...

Страница 11: ...an motors These switches stop the fan motors when the doors are open DOOR FRAME HEATERS This cabinet is equipped with both frame and door heaters These are ther mostatically controlled and will not come on until the cabinet is at operating tem perature See door mfg instructions for heater replacement at the back of this booklet ALARM THERMOSTAT Heater Delay The alarm heater delay thermo stat is lo...

Страница 12: ...These systems come pre charged for easy field installation If it should become necessary to leak test the system please adhere to the following notice NOTICE BECAUSE OF THE CFC AT MOSPHERIC CONSIDERATIONS BEING TAKEN TODAY WE ASK THAT LEAK TESTING BE DONE WITH REFRIGERANT 22 MIXED WITH NI TROGEN IF THE CONDENSING UNIT NAMEPLATE DESIGNATES A RE FRIGERANT OTHER THAN R 22 RE MOVE ALL R 22 FROM THE IM...

Страница 13: ...d quick connects optional COMPRESSOR The compressor is mounted on semi rigid rubber pads There are no mounting springs so the compressor is es sence becomes solid mounted DO NOT LOOSEN THE MOUNTING BOLTS ON THE COMPRESSOR FAN DELAY THERMOSTAT The fan delay thermostat is con nected to the left hand fan motor as you face the unit from the electrical box side and will leave this fan off at ambients b...

Страница 14: ...t the wiring diagram for proper wiring BOTTOM MOUNT VERSIONS The refrigeration line set is provided with quick connect connections on both ends for installation at the case and the remote unit The line set is tagged with the end that is to be attached at the case The line set is tagged with the end that is to be at tached at the case end Do not over tighten the quick con nects as this will damage ...

Страница 15: ... Dirty condenser 3 Clean High head pressure 1 Cabinet location too warm 1 Relocate cabinet 2 Restricted condenser air flow 2 Clean condenser to re move air flow restriction 3 Defective condenser fan motor 3 Replace 4 Air or non condensable gases in system 4 Leak check change drier evacuate and re charge 5 Defective fan delay ther mostat 5 Replace Warm storage temperatures 1 Temperature control not...

Страница 16: ...trol 1 Replace 2 Control feeder tube not in positive contract 2 Assure proper contract 3 Short on refrigerant 3 Leak check change drier evacuate and re charge Compressor will not start no noise 1 Blown fuse or breaker 1 Replace fuse or reset breaker 2 Defective or broken wir ing 2 Repair or replace 3 Defective overload 3 Replace 4 Defective temperature control 4 Replace 5 Power disconnected 5 Chec...

Страница 17: ...denser 6 Defective condenser fan motor 6 Replace 7 CRO not set properly 7 Reset to 10 psi Icing condition in drain pan 1 Low voltage 1 Check voltage at com pressor 2 Cabinet not level 2 Check front to rear level ing adjust legs accordingly 3 Defective drain tube heater 3 Replace 4 Defective drain pan heater 4 Replace LIGHTING SYSTEM Lights won t start 1 Check light switch 2 Check continuity to bal...

Страница 18: ...necessary 5 Check voltage 6 New bulbs tend to flicker until used Ballast hums 1 Check voltage 2 Replace ballast LIGHTING SYSTEM ELECTRICAL COMPONENTS MODEL HGL 1 T B HGL 2 T B HGL 3 T B Evaporator Fan Morrill SPB5EM2 Same Same Motor Light Ballast Huss 06 S183 1 06 S 183 1 1 06 S 183 2 2 06 S 183 2 1 Fluorescent lamp FO4OW T8 60 Same Same Page 18 ...

Страница 19: ...te of cabinet and if possible forward a copy of the original invoice or delivery receipt All shipments of in warranty replacement parts will be invoiced from the factory until such time as the defective part is returned and proved to be defective by our Quality Con trol Department Contact your Hussmann Distributor for instructions on returning in warranty parts Warranty parts must be returned to t...

Страница 20: ...rmined by the compressor serial number on the compressor serial plate For any defective compressor beyond the twelve or twenty month time period a salvage value credit will be given too partially offset the invoice for the replacement To obtain reimbursement forward to Hussmann Corporation 140 East State Street Gloversville NY 12078 the following information 1 The cabinet model and serial number 2...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ...LK JUMPER TO CONDENSING UNIT 3 TC2 WHT BLK ORN PUR EVAP FANS DEFROST CLOCK N X 4 1 2 3 T BRN BLU DOOR FRAME HEATERS 1 RED BLK RED RED RED BRN BLK BLK BLK DEFROST HTRS DRAIN TUBE HTRS DRAIN PAN HTRS FAN SWITCH ANTHONY FRAME LIGHT SWITCH DEFROST THERMOSTAT RED P BLK Z BLK ORN ORN BRN BLU DOOR HEATERS FRAME HEATERS RED BLK BLK BLK BLK BLK BLK BLK ALARM STAT GRD NOTE WIRES NOTED WITH ARE IN WIRE HARNE...

Страница 27: ...HTRS DRAIN TUBE HTRS DRAIN PAN HTRS FAN SWITCHES ANTHONY FRAME LIGHT SWITCH DEFROST THERMOSTAT RED P BLK Z BLK ORN ORN BRN BLU DOOR HEATERS FRAME HEATERS RED BLK BLK BLK BLK BLK BLK BLK ALARM STAT GRD BALLAST LAMP 5 4 3 2 7 6 9 8 1 10 ORN ORN BRN BRN LAMP RED BLU BLU BLK WHT RED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 15 16 HGL 2 B HGL 2 T...

Страница 28: ... HTRS DRAIN TUBE HTRS DRAIN PAN HTRS FAN SWITCHES ANTHONY FRAME LIGHT SWITCH DEFROST THERMOSTAT RED P BLK Z BLK ORN ORN BRN BLU DOOR HEATERS FRAME HEATERS RED BLK BLK BLK BLK BLK BLK BLK ALARM STAT GRD BALLAST LAMP 5 4 3 2 7 6 9 8 1 10 ORN ORN LAMP RED BLU BLU BLK WHT RED BALLAST LAMP 5 4 3 2 7 6 9 8 1 10 ORN ORN LAMP RED BLU BLU BLK WHT RED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 24...

Отзывы: