P/N 3053878_B 4-1
Roll-In
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
START UP / OPERATION
If a leak is detected, follow store safety procedures.
It is the store’s responsibility to have a written safety
procedures in place. The safety procedure must comply
with all applicable codes such as local fire department’s codes.
At minimum, the following actions are required:
• Immediately evacuate all persons from the store, and
contact the local fire department to advise them that a
propane leak has occurred.
• Call Hussmann and/or a qualified service agent and
inform them that a propane sensor has detected the
presence of propane.
• Do not let any persons back into the store until
the qualified service technician has arrived and that
technician advises that it is safe to return to the store.
• The propane gas used in the unit has no odor. The
lack of smell does not indicate a lack of escaped gas.
• A hand-held propane leak detector (“sniffer”) should
be used before any repair and/or maintenance is
attempted. All repair parts must be identical models to
the ones they are replacing.
• No open flames, cigarettes or other possible sources
of ignition should be used inside the building where
the units are located until the qualified service
technician and/or local fire department determines
that all propane has been cleared from the area and
from the refrigeration systems.
12 HOURS AFTER STARTUP CHECKLIST
• Check case temperature.
• Check if there is any CoreLink alarm.
• Check water connections for leaks or accumulation
of water.
• Verify the fans are running.
• Check compressor’s amperage, and validate with the
information on serial plate.
• Check the door operation again to ensure doors open
and close properly once the case is down to operating
temperature.
• Check that all inspection plates and covers have been
properly replaced.
• Inspect for any water accumulation due to incorrect
or unsealed penetrations where electrical or other
lines pass through insulated walls of the case.
• Verify that the lights are “ON”. If lights are “OFF”,
check the illumination schedule and circuit breaker
for the lights.
• Check the water outlet temperature from each
condensing unit. Water outlet temperature should be
less than 10° above water inlet temperature.
Possible hazardous condition. Follow
safety procedures outlined by store
safety management.
Due to risk of ignition resulting from
incorrect parts or improper service, only
Hussmann authorized personnel may
service this equipment.
Component parts shall be replaced only
with exact manufacturer and model
number components. FAILURE TO USE
AUTHORIZED TECHNICIANS COULD
RESULT IN AN EXPLOSION, DEATH,
INJURY AND PROPERTY DAMAGE.
Содержание DD5X5FRW
Страница 31: ...Roll In P N 3053878_B 2 11 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 U S A ...
Страница 33: ...Roll In P N 3053878_B 2 13 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 U S A CONTROLLER TROUBLESHOOTING ...
Страница 35: ...Roll In P N 3053878_B 2 15 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 U S A CONDENSING UNIT VIEWS ...
Страница 42: ...3 4 Drip Piping P N 3053878_B U S Canada 1 800 922 1919 Mexico 1 800 890 2900 WWW HUSSMANN COM NOTES ...
Страница 54: ...6 6 Hussmann Corporation 12999 St Charles Rock Road Bridgeton MO 63044 2483 www hussmann com ...