background image

r3(Cr3)-m/f-0608

18

refrigeration

Piping

The  refrigerant  line  outlets  are  located  under  the  case. 

Locate first the electrical box, the outlets are then on the 

same side of the case but at the opposite end. Insulate 

suction lines to prevent condensation drippage.

refrigeration lines

Liquid 

Suction

3/8" O.D.

5/8" O.D. 

note:   the standard coil is piped at 

5

/

8

" (suction); however, 

the store tie-in may vary depending on the number of 

coils and the draw the case has. depending on the case 

setup, the connecting point in the store may be 

5

/

8

", 

7

/

8

", 

or 1

1

/

8

". refer to the particular case you are hooking up.

Refrigerant  lines  should  be  sized  as  shown  on  the 

refrigeration legend furnished by the store.
Install 

P-traPS

 (oil traps) at the base of all suction line 

vertical risers.

Pressure drop

 can rob the system of capacity. To keep the 

pressure drop to a minimum, keep refrigerant line run as 

short as possible, using the minimum number of elbows. 

Where elbows are required, use long radius elbows only.

Control Settings

See R3(CR3)-M/F technical data sheet for the appropriate 

settings for your merchandiser. Maintain these parameters 

to achieve near constant product temperatures. Product 

temperature should be measured first thing in the morning, 

after  having  been  refrigerated  overnight.  Defrost  times 

should be as follows: OFF CYCLE - Defrost times should 

be as directed in the R3(CR3)-M/F technical data sheet. 

The number of defrosts per day and the duration of the 

defrost cycle may be adjusted to meet conditions present 

at your location.

access to thermostatic expansion valve (teX) and 

drain lines

mechanical -

 Remove product from end of case. Remove 

product  racks.  Remove  refrigeration  and  drain  access 

panels (labeled). TEX valve (mechanical only) and drain 

are located under each access panel at end of the case.

electronic - 

The Electronic Expansion valve master and 

slave cylinder(s) are located within the electrical access 

panel(s).

electronic expansion valve eev (optional)

A  wide  variety  of  electronic  expansion  valves  and  case 

controllers  can  be  utilized.  Please  refer  to  EEV  and 

controller  manufacturers  information  sheet.  Sensors  for 

electronic expansion valves will be installed on the coil inlet, 

coil outlet, and in the discharge air. (Some supermarkets 

require a 4th sensor in the return air). Case controllers will 

be located in the electrical raceway or under the case.

thermostatic expansion valve location

This device is located on the same side as the refrigeration 

stub. A balanced port expansion valve model is furnished 

as  standard  equipment,  unless  otherwise  specified  by 

customer.

expansion valve adjustment

Expansion  valves  must  be  adjusted  to  fully  feed  the 

evaporator.  Before  attempting  any  adjustments,  make 

sure the evaporator is either clear or very lightly covered 

with frost, and that the fixture is within 10°F of its expected 

operating temperature.

measuring the operating Superheat

1.   Determine the suction pressure with an accurate 

pressure gauge at the evaporator outlet.

.   From a refrigerant pressure temperature chart, 

determine the saturation temperature at the 

observed suction pressure.

3.   Measure the temperature of the suction gas at the 

thermostatic remote bulb location.

4.   Subtract the saturation temperature obtained in step 

No.  from the temperature measured in step No. 3. 

The difference is superheat.

5.   Set the superheat for 5°F - 7°F. 

evaporator Pressure regulator

An Evaporator Pressure Regulator is installed in the front 

of the self service section to maintain a constant discharge 

temperature. It is located at the front right side of the case, 

under the fan plenum near the TEX Valve.

Service Case temperature Control

Temperature control in the upper section of the CR3 with 

the Service Option is done by means of a thermostat and 

suction  solenoid  valve. This  controls  both  temperature 

and humidity.

thermostat (t-Stat) location

Thermostats are located within the electrical raceway. Refer 

to diagram below. There are also labels on the back of the 

case indicating T-STAT location(s).

T-Stat &

Ballast  Are

Labeled as

Such

Figure #3

Содержание CR3-F

Страница 1: ...ce and Self service Meat Fish case with rear storage P N R3 CR3 M F 0608 INSTALLATION OPERATION GUIDE CHINO R3 CR3 M F Combination Service and Self service Meat Fish case with rear storage Rev 0608 In...

Страница 2: ...nt Case R3 F Refrigerated Service Top for Fish with Gravity Coil and Refrig Self Service Front Case CR3 M Refrigerated Service Top for Meat with Gravity Coil and Refrig Self Service Front Case CR3 F R...

Страница 3: ...2 3 1 2 12 3 4 19 5 8 8 39 1 4 10 3 4 35 3 8 18 53 3 8 26 1 2 16 26 3 8 Optional Dry Refrigerated or no storage 19 3 8 4 R3 F Service Fish Case with Straight Glass Self Service Front Gravity Coil and...

Страница 4: ...OD LEG BRACES WHERE SUPPORT IS BEST TO PREVENT DAMAGE TO THE CASE 1 It is imperative that the cases be leveled from front to back and side to side as they are being joined beginning with the first cas...

Страница 5: ...Be careful to observe the area where the clamp is being tightened so that the case is not damaged as pressure is applied 8 Attach cases together via 2 bolts located in the end leg tubes at the base of...

Страница 6: ...x screws along glass clamp may have loosened during shipping Retighten all glass clamp screws before opening glass Level Minitop Hardware IF GLASS DOES NOT CLOSE STAY OPEN PROPERLY Level MINI TOP HARD...

Страница 7: ...If pinched at the bottom Gap is more narrow at the bottom than at the top Adjust outside hinges Center hinge stationary This diagram indicates that raising the outside hinges widens the gap at the bot...

Страница 8: ...most cases the center hinge is the first candidate but if the arm minicam is at its maximum or minimum position then obviously the outer hinges must be used See Vertical Adjustment of Glass Vertical...

Страница 9: ...op edge or center with 3 8 long sheet metal screws If needed use silicone sparingly to caulk the joint trim and exterior body panels with an appropriate colored silicone to ensure that a cleanable and...

Страница 10: ...3 M F 0608 10 Installation Cont d Scale Stand Installation Instructions 1 Set Scale Stand to desire location 2 Drill holes and screw in place with screws provided Hex Tek S S 10 16 X Note Use hole pat...

Страница 11: ...sure 10 inches from top of the case Note Line up 6 inch mark with 10 inch mark Step 3 Use bracket center hole to align with cross mark Note Use pencil marker to mark hole pattern HOLE PATTERN Step 4 D...

Страница 12: ...ion Cont d Step 6 Install upper support bracket Step 7 Mount wrap board on top of bracket using a spacer to have a gap between rear wall and board Step 8 Screw bracket into wrap board screws provided...

Страница 13: ...mper slide into the channel Step 3 Starting on one end while inserting the bumper push it up against the end cap to prevent the bumper from shrinking after installation when it gets cold Step 4 As you...

Страница 14: ...are positioned within the base grooves Roll vinyl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over the Rig...

Страница 15: ...th of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over the Rigid Base 3 If necessary wipe clean with any household cleaning produc...

Страница 16: ...legs are positioned within the base grooves Roll vinyl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over t...

Страница 17: ...sed as part of the condensate drain to prevent air leakage or insect entrance Store plumbing system floor drains should be at least 14 off the center of the case to allow use of the P TRAP pipe sectio...

Страница 18: ...c Expansion Valve EEV Optional A wide variety of electronic expansion valves and case controllers can be utilized Please refer to EEV and controller manufacturers information sheet Sensors for electro...

Страница 19: ...are operating at the proper temperature Allow merchandiser to operate a minimum of 6 hours before stocking with any product 5 When stocking never allow the product to extend beyond the recommended loa...

Страница 20: ...ct cleaning agents or cleaning cloths can cause micro scratching of the surface causing the plastic to haze over time Cleaning Hussmann recommends using a clean damp chamois or a paper towel marketed...

Страница 21: ...and hot water 2 Rinse with hot water but DO NOT flood or spray glass If you are working from the rear of the case the front glass is lift up glass and is NOT sealed IT WILL LEAK Keep all water within...

Страница 22: ...R3 CR3 M F 0608 22 Electrical Wiring Diagrams R3 2002 Meat 4 W0180016 6 W0180017 8 W0180018 12 W0180020 24VAC Solenoids 12 1H10019...

Страница 23: ...IL ASSY VA 08 0 120V 0 8A 225 02 0513 CAP OFF WIRE IF UNUSED T STAT 1 225 01 0707 SUCTION SOLENOID 1 225 01 3202 RJ 45 NETWORK JACK 125 01 0200 125 01 0203 125 01 0204 COMMUNICATION CONNECTION TO BE D...

Страница 24: ...25 01 3202 LOWER FRONT SECTION SHELF LIGHT OPTION A COIL ASSEMBLY 0 8A 120V 225 02 1333 BALLAST 125 01 3266 FULHAM LH3 120 L F21T5 36 125 03 1128 F21T5 36 125 03 1128 RJ 45 NETWORK JACK 125 01 0200 12...

Страница 25: ...5 48 125 03 1131 F28T5 48 125 03 1131 LOWER FRONT SECTION SHELF LIGHT OPTION A M M BONE COIL ASSY VA 08 0 120V 0 8A 2 225 02 0513 BALLAST 125 01 3266 FULHAM LH3 120 L RJ 45 NETWORK JACK 125 01 0200 12...

Страница 26: ...TAT 1 225 01 0707 SUCTION SOLENOID 1 225 01 3202 M M F28T5 48 125 03 1131 F28T5 48 125 03 1131 LOWER FRONT SECTION SHELF LIGHT OPTION A BOHN COIL ASSY VA 012 0 1 6A 120V 2 225 02 1333 BALLAST 125 01 3...

Страница 27: ...NOT WIRE A HEATING ELEMENT TO THE FIXED GLASS MEAT FISH R 3 2002 CASES LOWER FRONT SECTION OPTION B REFRIGERATED REAR STORAGE OPTION C TAG REAR STORAGE T STAT 1 225 01 0707 SUCTION SOLENOID 1 1H08061...

Страница 28: ...orm a complete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant acc...

Страница 29: ...warm product 2 Is the product loaded beyond the Safe Load Line markers 3 Are the return air ducts blocked 4 Are the entering air ducts blocked 5 Is a dumped display causing turbulent air flow and mix...

Страница 30: ...erature recovery Food store refrigerators are not food chillers nor can they reclaim quality lost through previous mishandling d Care must be taken when cross merchandising products to ensure that pot...

Страница 31: ...________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________...

Отзывы: