1.   Verify that AC power is switched OFF at the power source 

before beginning.

2.   Remove the junction box cover (two screws). 
3.   Use appropriate electrical conduit and fittings to route AC power 

wire into the junction box. Run high voltage power wiring in separate 

conduit from low voltage signal wiring.

4.   Connect the power wires to the 

transformer wires with wire nuts 

(see color code chart), and replace 

junction box cover. 

5.   Installer is responsible for local 

electrical codes and wiring.

Transformer

Hot 

Neutral

Safety Ground

 (required)

North America

 (115VAC)

Black

White

Green

International

 (230VAC)

Brown 

Blue

Green with yellow stripe

CONNECT AC POWER .............................................................................................................

�� �

�� �

��

�� �

�� �

���

�� ���������

�� �

�� �

������

���

�� �

�� �

����

�����������

�� ���

�� ���

��

��

��

��

���

���

��

������ �

������ �

������ �

������

������

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

����

����������

���������

����� ������

����� ����� ����

�����

����������

�����

��� �� ��� ���

��� ���

�� �

�� �

��

�� �

�� �

���

�� ���������

�� �

�� �

������

���

�� �

�� �

����

�����������

�� ���

�� ���

��

��

��

��

���

���

��

������ �

������ �

������ �

������

������

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

����

����������

���������

����� ������

����� ����� ����

�����

����������

�����

Содержание IMMS-CI-HW

Страница 1: ...former 24 VAC 24 VAC To Controller SEN AC Sensor 1 Sensor 2 Sensor 3 Sensor Common From SI or Previous CI To Next CI From Sensors IMMS Controller Interface Earth Ground Drain wires here POWER Controll...

Страница 2: ...ireless Connection 5 Earth Grounding 6 Power and Test 7 Green Button 7 To Address Controller Interfaces 8 Diagnostic Mode 8 Interface Reset 9 Additional Connections 9 Connections to Other Interfaces 9...

Страница 3: ...ble indoor or outdoor wall which will not receive spray from sprinklers Drive self tapping screws through recessed holes in plastic cabinet back into solid surface Ambient operating temperature must n...

Страница 4: ...high voltage power wiring in separate conduit from low voltage signal wiring 4 Connect the power wires to the transformer wires with wire nuts see color code chart and replace junction box cover 5 Ins...

Страница 5: ...by color code to the ICC power module terminals as shown CI 4 SI 4 AC SI 1 CI 1 REM To SmartPort SI 3 CI 3 Ground SEN SI 2 CI 2 From Transformer 24 VAC 24 VAC To Controller SEN AC Sensor 1 Sensor 2 S...

Страница 6: ...r power OFF strip wire ends approximately 1 4 6 mm and connect by color code to the terminals in the wiring compartment It is important to connect the red and white wires to the correct AC terminals R...

Страница 7: ...acket and excess foil shield back approximately 2 50 mm 3 Strip approximately 3 16 4 5 mm from each individual wire and connect to top half of communications terminals in area labeled From SI or Previ...

Страница 8: ...rounding terminal where labeled in interface 2 Route ground wire through low voltage conduit and secure to 8 ft 2 5 m copper clad ground rod driven vertically into earth 3 Ground connection should hav...

Страница 9: ...then back on The button allows the Controller Interface to receive an address from the SI and also to enter the diagnostic mode POWER AND TEST GREEN BUTTON LED lights to the left of the display indic...

Страница 10: ...ler LED will light as it communicates to the controller Radio check Immediately after the Run Station command is sent to the controller the radio if one is installed will transmit a continuous tone fo...

Страница 11: ...rect address INTERFACE RESET Turn off or disconnect AC power plug before making any connections inside the CI ADDITIONAL CONNECTIONS 1 To connect to additional Controller Interfaces route strip and co...

Страница 12: ...Connect one wire from sensor to Sensor 1 position on upper terminal strip 4 Connect other sensor wire to Sensor Common 5 Up to 3 sensors may be connected to the CI Connect one wire from each addition...

Страница 13: ...er terminals in the interface 3 This will double the yellow wires in each terminal one each from the interface transformer and one each from the sensor power 4 Route and connect the white sensor signa...

Страница 14: ...nect one of the white wires to the Sensor number and the other to Sensor Common FLOW CLIK IMMS CI 4 SI 4 AC SI 1 CI 1 REM To SmartPort SI 3 CI 3 Ground SEN SI 2 CI 2 From Transformer 24 VAC 24 VAC To...

Страница 15: ...controller connections 3 Connect the blue wire from SmartPort to the other blue position labeled To SmartPort Note The blue SmartPort connection is not shared with any other wires CONNECTION TO OPTION...

Страница 16: ...3 km Avoid splices in GCBL cable runs 18 AWG or 1 mm red white blue yellow green Used to connect interface to local controller up 6 ft 2 m GCBL 5 CONDUCTOR SPRINKLER WIRE Hunter Industries Incorporate...

Отзывы: