Hubbell Load:Logic Скачать руководство пользователя страница 8

 
 
 
 
 
 

PD2794                                 02/2017 

                                                                                                                     Page 3 

Understanding Low Voltage Load Capacity 

 
The room controller is capable of providing a source of 24VDC to power the connected low voltage devices such as switches, 
sensors  and  wireless  transmitters.   

The  room  controller’s  current  capacity  is  250  mA.    Since  the  control components  require 

different amounts of current to operate properly, the following table will help to determine how many low voltage devices can be 
connected  to  a  single  room  controller  regardless  of  the  RJ45  port  in  which  the  device  is  connected.    If  two  or  more  room 
controllers  are  connected  together,  the  capacity  is  determined  for  each  room  controller  based  on  the  control  devices  that  are 
actually  connected  into  that  specific  room  controller.  The  maximum  capacity  per  room  controller  is  30  Loads.    Below  is  the 
correlation in regards of current requirements per low voltage device. 
 

 

Switches, Daylight Photocell, and PIR Occupancy Sensor = 1 Load 

 

PIR only Occupancy sensor with RP option = 2 Loads 

 

Dual Technology and Ultrasonic Occupancy sensor = 3 Loads 

 

Dual Technology and Ultrasonic Occupancy sensor with RP option = 4 Loads 

 
NOTE: Only one daylight sensor can be connected in each room/zone 
 

Self-Configuration 
 

The 

room  controller’s  sequence  of  operation  will  automatically  reconfigure  as  devices  are  connected  as  described  in  the 

following sections. Note that self-configuration will automatically be disabled once the room has been manually configured. 

See 

Manual Configuration section.

 

 

Occupancy Sensors 

 
The room controller is compatible with any Hubbell Wiring Device-Kellems low voltage occupancy sensor.  An RJ45 wiring 
adapter (

sold separately

) is required to make the sensor compatible with the connection to a RJ-45 port in the room controller.  

See 

Figure 3

 and HBLRJ45A10 installation instructions

.  This adapter is color coded to match the flying leads on the sensors. 

 
An occupancy sensor connected to a room controller will be recognized after the first time it cycles occupancy. 
 
When ONLY an occupancy sensor is connected to the room controller, the room controller will set its operation mode to Auto 
ON / Auto OFF.  Once a smart switch is connected to the room controller, the operation mode will automatically switch to 
Manual ON / Auto OFF (vacancy mode).  To change one or more load(s) to Auto ON operation see Manual Configuration 
section below. 
 

Figure 3 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание Load:Logic

Страница 1: ...unit For Indoor use only Do not use outdoors Disconnect switch or a circuit breaker must be provided and marked as the disconnecting device The use of accessory equipment not recommended by the manuf...

Страница 2: ...splayed These will include 1 Room Controllers Touch to display a list of room controllers found in the room Touch one of the room controllers to see a display showing controls for the relay s and dimm...

Страница 3: ...ion after an outage Last State is the default setting Touch Set Level to enter a specific dim level for power up Use the Level slider to set the desired level or touch the box to use the keyboard to e...

Страница 4: ...Groups A blue background fill in one of the 16 available groups indicates that this switch is selected to be a member of this group number A gray background fill indicates that the switch is NOT a me...

Страница 5: ...ne of the 16 available groups indicates that this sensor is selected to be a member of this group number A gray background fill indicates that the sensor is NOT a member of the group By default the oc...

Страница 6: ...urned OFF NOTE Make adjustments to the Design Level until the desired foot candle reading is achieved on the light meter at the task surface E Test Mode This is the factory default setting for Zone 1...

Страница 7: ...rcuit s it controls The MAC address will be needed later during the system setup process 3 Turn power OFF at the service panel 4 Mount the room controller s enclosure to a knockout opening of an elect...

Страница 8: ...Occupancy sensor with RP option 4 Loads NOTE Only one daylight sensor can be connected in each room zone Self Configuration The room controller s sequence of operation will automatically reconfigure...

Страница 9: ...s RCSNFx and RCSTOx RCSRLx RCSSCx RCSNRLFx will self configure by default to their respective descriptions For example RCSRLx is a Raise Lower dimmer Its default operation will be to change ALL the li...

Страница 10: ...2 Observe that the button is located slightly offset from the bezel opening The LED marked SVC will blink while the configuration button is being pressed 3 Release the configuration button and note t...

Страница 11: ...Simultaneously press and hold buttons A and B for three seconds until LED A begins to blink rapidly This indicates the room controller has transitioned from load configuration mode into photocell con...

Страница 12: ...n is complete the room controller will automatically exit configuration mode and return to normal operation Daylight harvesting will now be active based on the settings made during configuration Reset...

Отзывы: