Hubbell Load:Logic Скачать руководство пользователя страница 11

 
 
 
 
 
 

PD2794                                 02/2017 

                                                                                                                     Page 6 

Assign a Load 

Deny a Load 

6.  Repeat the assignment process above for each load.  

 
Switches WITHOUT LED indicators, (

RCSOOx, RCSNRLFx, RCSRLx

, etc.): 

 

1.  Press the ON button or the Raise button to assign control of the load.  
2.  Press the OFF button or the Lower button to deny control of the load. 
3.  Tap the recessed configuration button to advance to the next load as necessary. 

 
After all loads are assigned, exit manual configuration mode. Test the button operation and repeat the above if 
necessary. 
 
 

Configure Loads for Auto ON or Manual ON (Vacancy Mode) Operation 

 

1.  Enter 

Manual Configuration Mode from the Room Controller

 (see section above).   

2.  While load A is ON, the B LED indicator light on the room controller will identify the current operation mode for the load.   

 

a.  If LED B is OFF, the load will operate in manual on (vacancy) mode. 
b.  If LED B is ON, the load will operate in auto ON mode when the motion sensor detects occupancy. 

 

3.  Press and release button B on the room controller to change the operation mode for the current load. 
4.  To advance to the next load, press and release button A on the room controller. 
5.  Repeat the above for all loads. 
6.  When finished, exit manual configuration mode. 

 

Hint:  a  load  set  to  Manual  ON  (vacancy)  mode  must  be  controlled  by  an  RCSx  smart  switch,  otherwise  the  load  will 
never turn ON. 

 

Photocell Configuration Mode

 

 

1.  Set the room controller to manual configuration mode.  

See 

Manual Configuration Mode from the Room Controller 

section

 

on page 5

2.  Simultaneously press and hold buttons A and B for three seconds until LED A begins to blink rapidly. This indicates the 

room controller has transitioned from load configuration mode into photocell configuration mode. 

3.  While in photocell configuration mode, only one load will be ON.  If the selected load has dimming capability, the light 

will cycle between minimum to maximum light levels to identify itself during the selection process. 

4.  Press and release button B on the room controller.  LED B will blink in a pattern to indicate the performance level for 

daylight harvesting.  The blink patterns are as follows: 
 

a.  Double blink/pause indicates normal baseline performance (default setting). 
b.  Triple blink/pause indicates more aggressive performance, lights will dim more. 
c. 

Single blink/pause indicates less aggressive performance, lights will dim less. 

d.  No blinking indicates that the selected load will not participate in daylight harvesting. 

 

5.  Press and release button B on the room controller to cycle through the performance choices for the selected load. The 

“more  aggressive”  selection  will  cause  the  light  level  to  be  reduced  more  during  daylight  harvesting.  The  “less 
aggressive” selection will cause the light level to be reduced less.  

 
Hint: As a default, if the room controller is equipped with dimming capability (LLC2RD), the photocell will operate in 
continuous dimming daylight harvesting mode.  If the room controller does not have dimming capability (LLR2R), the 
photocell will operate in switching (ON/OFF) daylight harvesting mode based on a default set point of 150 foot-candles.

 

 

6.  Press and release button A on the room controller save your selection and to advance to the next load. 

Содержание Load:Logic

Страница 1: ...unit For Indoor use only Do not use outdoors Disconnect switch or a circuit breaker must be provided and marked as the disconnecting device The use of accessory equipment not recommended by the manuf...

Страница 2: ...splayed These will include 1 Room Controllers Touch to display a list of room controllers found in the room Touch one of the room controllers to see a display showing controls for the relay s and dimm...

Страница 3: ...ion after an outage Last State is the default setting Touch Set Level to enter a specific dim level for power up Use the Level slider to set the desired level or touch the box to use the keyboard to e...

Страница 4: ...Groups A blue background fill in one of the 16 available groups indicates that this switch is selected to be a member of this group number A gray background fill indicates that the switch is NOT a me...

Страница 5: ...ne of the 16 available groups indicates that this sensor is selected to be a member of this group number A gray background fill indicates that the sensor is NOT a member of the group By default the oc...

Страница 6: ...urned OFF NOTE Make adjustments to the Design Level until the desired foot candle reading is achieved on the light meter at the task surface E Test Mode This is the factory default setting for Zone 1...

Страница 7: ...rcuit s it controls The MAC address will be needed later during the system setup process 3 Turn power OFF at the service panel 4 Mount the room controller s enclosure to a knockout opening of an elect...

Страница 8: ...Occupancy sensor with RP option 4 Loads NOTE Only one daylight sensor can be connected in each room zone Self Configuration The room controller s sequence of operation will automatically reconfigure...

Страница 9: ...s RCSNFx and RCSTOx RCSRLx RCSSCx RCSNRLFx will self configure by default to their respective descriptions For example RCSRLx is a Raise Lower dimmer Its default operation will be to change ALL the li...

Страница 10: ...2 Observe that the button is located slightly offset from the bezel opening The LED marked SVC will blink while the configuration button is being pressed 3 Release the configuration button and note t...

Страница 11: ...Simultaneously press and hold buttons A and B for three seconds until LED A begins to blink rapidly This indicates the room controller has transitioned from load configuration mode into photocell con...

Страница 12: ...n is complete the room controller will automatically exit configuration mode and return to normal operation Daylight harvesting will now be active based on the settings made during configuration Reset...

Отзывы: