2

INSTALLATION

NOTE: Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency ballast 
must be fed from the same branch circuit as the AC ballast.

  1.  Disconnect  AC  power  from  the  fixture.  Remove  the  

ballast channel cover and install the emergency ballast 
in the ballast channel (see Illustration 1).

  2.  Select  the  appropriate  wiring  diagram  to  connect 

the  emergency  ballast  to  the  AC  ballast  and  lamp. 
Make sure all connections are in accordance with the  
National Electrical Code and any local regulations.

  3.  Refer to Illustration 2 and install the test switch through 
 

  the ballast channel cover of a troffer or through the side 

of a strip fixture. Drill a 1/2" hole and install the switch 
as  shown. Wire  the  test  switch  so  that  it  removes  AC 
power  from  both  the    emergency  ballast  and  the  AC 
ballast at the same time (see wiring diagrams section of  
these instructions).

  4.  Refer  to  Illustration  3A  or  3B  and  install  the  charging 

indicator light so that it will be visible after the fixture is 

 

  installed.

  5.  In  a  readily  visible  location,  attach  the  label  

“CAUTION–  This  Unit  Has  More  Than  One  Power  
Connection  Point.  To  Reduce  The  Risk  Of  Electric 
Shock,  Disconnect  Both The  Branch  Circuit-Breakers 
Or  Fuses  And  Emergency  Power  Supplies  Before  
Servicing.” 

  6.  After  installation  is  complete,  supply  AC  power  to  the 

emergency ballast and join the inverter connector.

  7.  A  short-term  discharge  test  may  be  conducted  after 

the emergency ballast has been charging for one hour. 
Charge  for  24  hours  before  conducting  a  long-term  
discharge test.  Refer to OPERATION.

NOTE:  After  installing  the  charging  indicator  light  and  test  switch,  mark  each  with  the  appropriate  label.  If  a  

detached charging indicator light is used, connect by matching wire colors and install as shown on the 
installation insert page.

WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT 

LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT jOIN 

INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED 

TO THE EMERGENCY BALLAST.

ILLUSTRATION 3B

STEP 2

ILLUSTRATION 3A

ILLUSTRATION 1

ILLUSTRATION 2

STEP 1

Fixture

Test Button

Hex Nut

Hex Nut

Test Switch

Leads

Push to Test

Charging

Indicator

Light

1/2" White

Bushing

Violet (+)

 

Brown (–)

Violet (+)

 

Brown (–)

1/2" White

Bushing

5/8" Black

Bushing

5/8" Black

Bushing

1/2" Punch

Fixture

Fixture

Charging

Indicator

Light