OPERATION
With AC power applied, the charging indicator light is illuminated, indicating that the battery is being charged.
When power fails, the emergency ballast automatically switches to emergency power, operating one lamp at
reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays
AC ballast operation for five seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits. This
emergency ballast will operate 14 W through 55 W lamps for a minimum of 90 minutes.
MAINTENANCE
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked
periodically to ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. One lamp
should operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. One lamp should operate at reduced illumination for at
least 90 minutes.
REFER ANY SERVICING INDICATED BY THESE CHECkS TO QUALIFIED PERSONNEL.
3
LAMP
RED
YEL/BLK
YELLOW
BLU/WHT
BLUE
1 LAMP
RAPID
START
BALLAST
RED
BLUE
BLUE
RED
WHT
BLK
WHITE
B
A
L
L
A
S
T
VIOLET
BROWN
WHT/BLK
BLK
E
M
E
R
G
E
N
C
Y
RED
WHITE
TEST
SWITCH
HOT
WHT/RED
CHARGING
INDICATOR
LIGHT
INVERTER
CONNECTOR
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
COM
BLK
WALL SWITCH
LAMP
RED
YEL/BLK
YELLOW
BLUE
1 LAMP
INSTANT
START
BALLAST
WHT
BLK
BLUE
RED
BLU/WHT
WHITE
B
A
L
L
A
S
T
VIOLET
BROWN
WHT/BLK
BLK
E
M
E
R
G
E
N
C
Y
RED
WHITE
TEST
SWITCH
HOT
WHT/RED
CHARGING
INDICATOR
LIGHT
INVERTER
CONNECTOR
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
COM
BLK
WALL SWITCH
)
(EMERGENCY
LAMP 1
LAMP 2
RED
YEL/BLK
YELLOW
BLU/WHT
BLUE
2 LAMP
RAPID
START
BALLAST
RED
BLUE
WHT
BLK
RED
BLUE
YELLOW
YELLOW
WHITE
B
A
L
L
A
S
T
VIOLET
BROWN
WHT/BLK
BLK
E
M
E
R
G
E
N
C
Y
RED
WHITE
TEST
SWITCH
HOT
WHT/RED
CHARGING
INDICATOR
LIGHT
INVERTER
CONNECTOR
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
COM
BLK
WALL SWITCH
)
(EMERGENCY
LAMP 1
RED
YEL/BLK
YELLOW
BLUE
2 LAMP
INSTANT
START
BALLAST
WHT
BLK
BLUE
RED
BLU/WHT
LAMP 2
BLUE
WHITE
B
A
L
L
A
S
T
VIOLET
BROWN
WHT/BLK
BLK
E
M
E
R
G
E
N
C
Y
RED
WHITE
TEST
SWITCH
HOT
WHT/RED
CHARGING
INDICATOR
LIGHT
INVERTER
CONNECTOR
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
COM
BLK
WALL SWITCH
FIG 119 ONE (1) LAMP INSTANT START BALLAST
FIG 99
ONE (1) LAMP RAPID START BALLAST
FIG 100 TWO (2) LAMP RAPID START BALLAST
FIG 104 TWO (2) LAMP INSTANT START BALLAST
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION