background image

4

3. Primary ammeter: monitor the output current value of "L1, L2" terminal.

V.Instructions

1. Before turning on the power, turn off the "power control" switch, and adjust the "A

phase adjustment", "B phase adjustment" and "C phase adjustment" counterclockwise to

zero.

2. Turn on the power, connect the "power input" A, B, C, and N terminals to a three-phase

four-wire power supply, and then connect the "A, B, C phase current output" terminals to

the device under test with special test leads.

3. After the connection is completed, close the "Power Control" switch, press the "Start"

button, and clockwise adjust the required test current for "A phase adjustment", "B phase

adjustment" and "C phase adjustment"), and then press " Stop” button and press the

“Start” button again to perform characteristic tests on the tested switch, circuit breaker,

and bus.

4. For the operation of lack of phase and unbalanced operation of three phases, only one

phase needs to be disconnected or adjusted to zero and open.

5. If there is only 220V power supply on site, you can short-circuit the ABC input to the

live wire of the power supply, and connect the N of the equipment to the neutral wire;

other operation methods are the same as 1, 2, 3, and 4.

VI.Safety Precautions

(1) For the safety of the operator and the instrument, ensure that the instrument is well

grounded.

(2) Connect the ground wire first when preparing for the test, and remove the ground wire

last when the work is completed.

(3) The power supply connected to the instrument is required to be able to withstand the

impact of 30A current.

(4) When connecting the instrument to the test product, pay attention to check whether

each wiring is wrong, so as to avoid damage to the equipment due to incorrect wiring.

(5) The maximum current value of the set over-current protection should not exceed the

rated output current value of the instrument.

Содержание HZDL-2000III

Страница 1: ...HZDL 2000III Primary Current lnjection Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Страница 2: ...anual and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this i...

Страница 3: ...Contents I Overview 1 II Technical features 2 III Working principle 2 IV Panel description 3 V Instructions 4 VI Safety Precautions 4 VII Transportation and maintenance 5 VIII Packing list 6...

Страница 4: ...teristics Use beautiful and generous PVC panel Display the primary current directly which is convenient for test observation and recording High measurement accuracy 0 5 level High power strong load ca...

Страница 5: ...ripple coefficient is less than 0 3 Standard sine wave 2 6 Measurement accuracy using 0 2S grade material is actually about 0 3 each current can be smoothly and continuously adjustable and the accurac...

Страница 6: ...igital real time acquisition method by measuring the voltage signal amplitude according to the voltage proportional relationship the high voltage measured voltage value can be calculated and the autom...

Страница 7: ...the operation of lack of phase and unbalanced operation of three phases only one phase needs to be disconnected or adjusted to zero and open 5 If there is only 220V power supply on site you can short...

Страница 8: ...n dust and mechanical damage 2 Storage The instrument should be stored in a ventilated non corrosive room with an ambient temperature of 20 60 relative humidity not exceeding 85 It should not be place...

Страница 9: ...6 VIII Packing list Attached picture system wiring No Name Qty 1 Test line 3 meters 12 2 Test line 1 square 6 3 Ground wire 1 4 Zero line 1 5 power cable 1...

Отзывы: