15
3. After you perform the settings, the
Bypass mode
and
No battery
alarms are reported by the
MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
4. View the system running status diagram on the MDU to check that the UPS is working in bypass
mode.
System User
LCD Preset Password
WebUI Preset Password
admin (system administrator)
000001
Changeme
operator (common user)
000001
Changeme
To ensure system security,
change the LCD and WebUI
passwords after the first login.
NOTE
1. On the main menu, choose
Common Functions
and tap
Inv. ON
.
2. In the displayed login window, enter the user name and
password, and tap .
3. In the displayed dialog box, tap
Yes
to start the inverter.
Starting inverter
5.3