10
8. Connect the output power cable.
9. Connect signal cables.
Scenario 2: Routing Cables from the Bottom
A cable entry cabinet needs to be installed when cables are routed from the bottom. This
document uses the cable entry cabinet installed on the right of the UPS cabinet as an example.
1. (Optional) Determine the installation
position for the cable entry cabinet, and
draw mounting holes in the installation
position based on drawings.
2. Remove the right and rear covers from the
UPS cabinet, and remove the front and rear
covers from the cable entry cabinet. Put away
the removed screws and covers.
3. Adjust the anchor bolts of the cable entry
cabinet to make it flush with the UPS cabinet.
4. Install equipotential plate mounting kits on the
same horizontal plane of the UPS cabinet and
cable entry cabinet.