UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
3 Installation
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
64
Figure 3-27
Securing the antiseismic kits to the cabinet
Step 5
Adjust the cabinet to ensure that the expansion bolts holes align with the beneath twelve half
holes.
Step 6
Use twelve M12 x 60 expansion bolts to firmly lock the four front and rear antiseismic kits to
the ground, as shown in
Figure 3-28
Locking the antiseismic kits to the ground
Step 7
Reinstall the support baffle plates and rear covers in the cabinet.
Step 8
Install the front and rear anchor baffle plates and left and right anchor baffle plates.
----End