UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
8 Technical Specifications
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
182
8.5 Bypass Input Electrical Specifications
Bypass Input
Specifications
400 kVA
500 kVA
Input format
Three-phase, four-wire, and PE
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Rated frequency
50 Hz or 60 Hz
Frequency range
±6 Hz (0.5–6 Hz, ±2 Hz by default)
Input mode
The main and bypass inputs are supplied by one or two power
sources.
Bypass current
sharing
In a parallel system, control the cable length to equalize the current.
The current unbalance must be less than 25%.
8.6 Battery Electrical specifications
Item
400 kVA
500 kVA
Battery voltage
360–552 V DC (30–46 batteries, 32 by default. The UPS5000-A
power is derated by 6% when 30 batteries are configured.)
Battery management Intelligent battery management
One-button cold-
start
In the case of mains outage, batteries start the UPS5000-A, which
supplies power to loads.
Battery string
sharing
Battery string sharing is supported in a parallel system. No battery
string is shared by default.
Charge voltage
Equalized voltage: 2.35 V/cell
Float voltage: 2.25 V/cell
In monitoring and power versions earlier than V100R001C10SPC008, the battery voltage is 360–480 V
DC (30 to 40 batteries, 32 by default).
8.7 Output Electrical Specifications
Item
400 kVA
Output system
Three-phase, four-wire, and PE wire
Voltage
380 V AC, 400 V AC, or 415 V AC (tolerance ±1%)