Name
Display
Description
Equalized charge
voltage
● Default value: 56.0 V
● Value range: 48.0–
57.0 V. The value
increases by 0.1 V
each time you press
SELECT.
Float charge
voltage
● Default value: 56.0 V
● Value range: 48.0–
57.0 V. The value
increases by 0.1 V
each time you press
SELECT.
Low DC cut-off
voltage
● Default value: 43.5 V
● Value range: 40.0–
54.0 V. The value
increases by 0.1 V
each time you press
SELECT. The low DC
cut-off voltage is
fixed at the current
value regardless of
the load percentage.
Set the
communications
address
The default
communications
address is 001, which is
used for the RS485
communications ports
(connect to northbound
devices). Set different
communications
addresses for parallel
UPSs.
Restore factory
settings
Disable the function of
restoring default setting
(default).