10
1. The UPS2000-G-15KRTL/20KRTL can connect to an external battery string (40 batteries
in the standard configuration, and an even number of 32 to 40 batteries are supported).
The neutral wire is connected to the middle point of the battery string. For example, if
there are 40 batteries, the neutral wire is connected to the negative terminal of the
twentieth battery.
2. When an external battery string is connected, install a DC circuit breaker (63 A, 600 V
DC) between the battery string and the UPS.
3. When an external battery string is connected, connect positive terminals in series by
using the two poles of the DC circuit breaker.
3
Installing Battery Cables
Ground
point
External
battery string
Battery 1
Battery 20
Battery 40
Wiring
Terminal
BATT.
±
240 V
DC
External
Circuit
Breaker
63 A
Cable
Cross-
Sectional
Area
16 mm
2
Terminal
Type
OT-16 mm
2
-
M6-90
°
terminal
External Battery Strings
Scenario 1
External Battery Packs
Scenario 2
1. A 15 kVA/20 kVA UPS with long backup time requires serial connection of two battery packs
in each group. A maximum of four groups with eight battery packs can be connected in
parallel. If more than two battery packs need to be connected to the 15 kVA/20 kVA UPS
with long backup time, the battery packs should be connected in parallel and then
connected to the battery input ports of the UPS, as shown in the following figure. Connect
battery packs 1 and 2 in series, battery packs 3 and 4 in series, battery packs 5 and 6 in
series, and battery packs 7 and 8 in series. Connect battery packs 1, 3, 5, and 7 in parallel
and battery packs 2, 4, 6, and 8 in parallel.
2. For more information, see the
ESS-240V12-(9AhBPVBA, 7AhBPVBA) Quick Installation Guide
.
M6 (5 PCS)
4.8 N•m