8
Parameter
UI Display Remarks
Number of
batteries
05 NO.
Set the number of batteries based on the actual battery quantity.
•
Professional version with standard backup time: 20 batteries; standard
version with standard backup time: 16 batteries, not configurable
•
UPS with long backup time: 16 batteries by default; value range: 16–
20
Total battery
capacity
06 CAP
Set this parameter to the total capacity of all batteries actually connected.
•
6 kVA UPS with standard backup time: 7 Ah, not configurable; 10 kVA
UPS with standard backup time: 9 Ah, not configurable
•
6 kVA UPS with long backup time: 40 Ah by default; 10 kVA UPS with
long backup time: 65 Ah by default; value range: 7–999 Ah
Charge
current limit
07 CL
•
Set this parameter to the maximum charge current in equalized charge
mode based on actual conditions.
•
6 kVA or 10 kVA UPS with standard backup time: 2 A, not configurable
•
6 kVA or 10 kVA UPS with long backup time: 4 A by default; value
range: 1–8 A, at an interval of 0.5 A
Set the output voltage level.
Start
Set the output frequency system.
Set the number of batteries.
End
No: UPS with long
backup time
Check that the input is normal
UPS with standard backup time?
On the default screen, hold down for more than 5 seconds. Release the button when you
hear a beep tone.
Set the total battery capacity.
After you ensure that the UPS runs properly, close the AC output circuit breakers on the rear
panel of the UPS (only for professional version), close the UPS AC output circuit breaker to
supply power to the loads.
Set the charge current limit.
Yes
The following figures show the parameter setting screen for a 10 kVA standard UPS with long
backup time working in normal mode.