UG10000079
13
0
13
0
313
.5
1
Installing the UPS
3
1. Before installation, read the UPS2000-A-(6 kVA-10 kVA) User Manual to get familiar
with UPS information and safety precautions.
2. Use fully insulated tools during installation and operation.
3. Only engineers certified by the manufacturer or its agents are allowed to perform UPS
installation, commissioning, and maintenance. Otherwise, personal injury or equipment
damage may occur, and the resulting UPS faults are beyond the warranty scope.
Mounting bracket
(optional)
M6x12 (4 PCS)
3 N•m
Unit: mm
M12x60 (4 PCS)
45 N•m
Mounting brackets can be configured for a UPS with standard backup time and a battery
box, but not for a UPS with long backup time.
Move the UPS to the installation position and press down the brake pads on the casters to secure
the UPS.
If mounting brackets are configured, install the mounting brackets on the UPS using M6x12 bolt
and secure the UPS to the floor using M12x60 expansion bolts.
Brake pad
Installation a Single UPS
2
Installing AC Input and Output Power Cables
1. Connect UPS AC input and output terminals L, N correctly. For a UPS with long backup time,
connect the battery terminals correctly.
2. Before connecting cables, ensure that the input and output circuit breakers are OFF. For a
UPS with long backup time, ensure that the battery circuit breakers are OFF. Perform all tasks
with the power off.
The UPS can generate high leakage current. A circuit breaker with leakage current protection
is not recommended. If leakage current protection is required, use the recommended model.