background image

17

2

Symptom

Possible Cause

Measure

The mains switch is ON. The 
LCD does not display 
anything. The system does 
not perform self-tests.

The input power supply 
is not connected.
The input voltage 
exceeds the limit.

Check the input power cable connection.
Use a multimeter to check that the UPS 
input voltage meets specifications.

The mains is normal, but the 
AC input indicator is off. The 
UPS runs in battery mode.

The mains switch is OFF.
The input power cable is 
not securely connected.

Turn on the mains switch.
Check the input power cable connection.

The UPS does not report 
faults, but has no output 
voltage.

The output power cable 
is not securely 
connected.

Check the output power cable connection.

The UPS does not start after 
you press       . 

is not pressed long 

enough. 
Overload occurs.

Press        for more than 5 seconds until 
you hear a beep sound.
Disconnect all loads, and restart the UPS.

The Mains indicator is off.

The mains voltage or 
frequency exceeds the 
UPS input range.

Use a multimeter to check that the input 
voltage and frequency meet specifications.

The battery discharge time is 
much less than the standard 
time.

Batteries are not fully 
charged.
The battery performance 
deteriorates.

Charge batteries for more than 8 hours 
when the mains is normal. Test the 
discharge time again.
Contact local Huawei technical support 
to replace batteries.

Abnormal noises or smell is 
generated in the UPS 
cabinet.

The UPS is faulty.

Shut down the UPS immediately and cut 
off the input power supply. Contact local 
Huawei technical support.

The battery indicator is 

blinking yellow. The buzzer 
buzzes 1 second and then 
stops 1 second. The battery 
capacity is insufficient. The 
UPS is shutting down.

The remaining battery 

capacity is insufficient. 
The UPS is shutting 
down, and the loads are 
powering off.

Save load data immediately and power 

off critical loads.
Connect UPS input terminals to the 
backup AC power supply.

Troubleshooting

Содержание UPS2000-A-10KTTL-P

Страница 1: ...0 HUAWEI TECHNOLOGIES CO LTD UPS2000 A 6 kVA 10 kVA Quick Guide Issue 04 Part Number 31506975 Date 2020 09 11 ...

Страница 2: ...me 67 UPS2000 A 10KTTL S 10 kVA standard version with long backup time 21 UPS2000 A 10KTTS P 10 kVA professional version with standard backup time 79 UPS2000 A 10KTTL P 10 kVA professional version with long backup time 22 Introduction 6 kVA 10 kVA Standard Version with Standard Backup Time 6 kVA 10 kVA Standard Version with Long Backup Time 1 AC input circuit breaker 2 Optional card slot under the...

Страница 3: ...urity protection mechanism supported 5 MBS port 6 Parallel cable port 7 Micro switch under the cover 8 Maintenance bypass circuit breaker 9 AC output circuit breaker 10 AC input terminal under the cover 11 Single UPS jumper terminal under the cover 12 AC output terminal under the cover 13 Battery wiring terminal under the cover UG10000006 1 2 3 4 5 10 6 11 12 9 8 7 UG10000007 1 2 3 4 5 6 9 8 7 10 ...

Страница 4: ...ong backup time Move the UPS to the installation position and press down the brake pads on the casters to secure the UPS If mounting brackets are configured install the mounting brackets on the UPS using M6x12 bolt and secure the UPS to the floor using M12x60 expansion bolts Brake pad Installation a Single UPS 2 Installing AC Input and Output Power Cables 1 Connect UPS AC input and output terminal...

Страница 5: ...N m UPS2000 A 6KTTL S M4 6 PCS 1 4 N m UPS2000 A 6KTTL S M5 6 PCS 2 8 N m 6 kVA 10 kVA Professional Version with Standard Backup Time 6 kVA 10 kVA Professional Version with Long Backup Time UPS2000 A 6KTTS P M4 6 PCS 1 4 N m UPS2000 A 10KTTS P M5 6 PCS 2 8 N m UPS2000 A 6KTTL P M4 6 PCS 1 4 N m UPS2000 A 6KTTL P M5 6 PCS 2 8 N m UG10000089 UG10000090 Mains AC load Mains AC load Short circuit bar S...

Страница 6: ...ker for the 10 kVA model 3 One or two battery boxes can be connected For details see the ESS 240V12 2x 9AhBPVBA 7AhBPVBA Quick installation Guide If longer backup time is required choose a battery rack Model UPS2000 A 6KTTL S UPS2000 A 6KTTL P UPS2000 A 10KTTL S UPS2000 A 10KTTL P Wiring Terminal BATT BATT External Circuit Breaker 50 A 63 A Cable Cross sectional Area 6 mm2 10 mm2 Terminal Type OT ...

Страница 7: ...down Back On the default screen in inverter mode hold down ESC for more than 5 seconds Release the button when you hear a beep tone The inverter shuts down On any other screen press ESC to return to the upper level menu the default screen is the upper level screen for the main menu screen Up Press or to scroll upward or downward You can set a value by using the list or step increase or decrease Do...

Страница 8: ...ng battery parameters compromises battery safety and battery backup time For details about parameter settings see the UPS2000 A 6 kVA 10 kVA User Manual 2 Set system parameters with caution because the settings determine normal UPS operation Setting Key UPS Parameters 5 2 Parameter UI Display Remarks Output voltage level 01 VOT For standard version the optional values include 220 V 230 V and 240 V...

Страница 9: ...mum charge current in equalized charge mode based on actual conditions 6 kVA or 10 kVA UPS with standard backup time 2 A not configurable 6 kVA or 10 kVA UPS with long backup time 4 A by default value range 1 8 A at an interval of 0 5 A Set the output voltage level Start Set the output frequency system Set the number of batteries End No UPS with long backup time Check that the input is normal UPS ...

Страница 10: ...s beyond the configured range the UPS has no output 1 Shut down loads 2 Perform shutdown operations on the UPS The inverter shuts down and the UPS transfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 3 Open the upstream AC input circuit breaker for the UPS the AC input circuit breakers on the rear panel of the UPS the AC output circuit breakers on the...

Страница 11: ...d version does not 2 This section describes how to install a 1 1 parallel system A maximum of four UPSs can be connected in parallel 6 kVA 10 kVA Professional Version with Standard Backup Time UPS2000 A 6KTTS P M4 12 PCS 1 4 N m UPS2000 A 10KTTS P M5 12 PCS 2 8 N m 1 2 3 4 5 6 1 AC input circuit breaker of UPS 1 2 AC input circuit breaker of UPS 2 3 AC output circuit breaker of UPS 1 4 AC output c...

Страница 12: ...PORT1 PORT2 UPS 2 UPS 1 This section describes the cable connection method for a 1 1 parallel system Refer to this method to connect the cables in other scenarios UPS2000 A 6KTTL P M4 12 PCS 1 4 N m UPS2000 A 10KTTL P M5 12 PCS 2 8 N m UPS 1 UPS 2 External power distribution provide by the customer Mains AC load 1 AC input circuit breaker of UPS 1 2 AC input circuit breaker of UPS 2 3 AC output ci...

Страница 13: ...as passed all check items described in chapter 5 Verifying the Installation Close the external battery circuit breakers if there are Close the general AC input circuit breaker for UPSs each branch input circuit breaker and the AC input circuit breakers on the rear panels of UPS 1 and UPS 2 Start End No Start the UPS in battery mode Yes Start the UPS in normal mode Powering On the UPS 6 1 Setting K...

Страница 14: ...nsfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 1 Shut down loads 2 Perform shutdown operations on each UPS in the parallel system All inverters shut down at the same time and the parallel system transfers to bypass mode If the bypass voltage is beyond the configured range the UPS has no output 3 Open the AC input circuit breaker on each UPS the gen...

Страница 15: ...1 VOT Output voltage level 02 FRE Output frequency system 03 BVU Maximum bypass voltage 04 BVL Minimum bypass voltage 05 NO Number of batteries 06 CAP Total battery capacity 07 CL Charge current limit 08 EOD EOD mode 09 DT Discharge time protection setting 10 ECO ECO mode enabling 11 VU Maximum ECO voltage 12 VL Minimum ECO voltage 13 FR ECO frequency range 14 S P Single UPS or parallel system ava...

Страница 16: ...ranges and no fault or alarm information is displayed If an alarm is present rectify the fault by checking the device status and parameters Abnormal noise No abnormal noise is generated Check where the abnormal noise comes from especially fans input and output transformer if configured If the problem is not resolved contact Huawei technical support Cleanliness Wipe the cabinet surface using a whit...

Страница 17: ...and current of the battery string as well as the voltage of each battery 3 Check the battery surface temperature 4 Keep deformed and bulged faulty batteries still for 30 minutes and then check and record open circuit voltage of the faulty battery 5 If the fault persists contact Huawei technical support Battery management parameters Parameters settings of battery number battery capacity battery cha...

Страница 18: ...ads and restart the UPS The Mains indicator is off The mains voltage or frequency exceeds the UPS input range Use a multimeter to check that the input voltage and frequency meet specifications The battery discharge time is much less than the standard time Batteries are not fully charged The battery performance deteriorates Charge batteries for more than 8 hours when the mains is normal Test the di...

Страница 19: ...ecome normal and manually clear the alarm Abnorma l BPS volt 0A 1 Possible cause The bypass input voltage is abnormal Measure Check whether the bypass input voltage is out of the specified range If the voltage is out of the specified range change the range setting or wait for the bypass input to recover 2 Possible cause The bypass frequency is out of the 45 55 Hz mapping to 50 Hz or 55 65 Hz mappi...

Страница 20: ...leared Possible cause The number of batteries configured is less than the actual number of batteries Measure Check whether the number of batteries is correctly set Battery overvoltage protection 20 1 Possible cause The number of batteries configured is less than the actual number of batteries Measure Check that the configured number of batteries is consistent with the actual number Possible cause ...

Страница 21: ...nected are loose Measure Check that parallel cables are securely connected Possible cause Parallel cables are damaged Measure Replace the parallel cables 2 4 5 Parallel cable alarm 54 2 Possible cause The parallel cables connected are loose Measure Check that parallel cables are securely connected Possible cause The parallel cables are damaged Measure Replace the parallel cables 3 EPO 55 1 Possibl...

Отзывы: