TP48120A-HD15A1 & TP48120A-HD15A2 &
TP48200A-HD15A1 & TP48200A-HD15A2
Installation Guide
10 Commissioning
Issue 03 (2014-12-02)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
68
Main
Menu
Second-
Level
Menu
Third-
Level
Menu
Fourth-Level
Menu
Default
Value
Setting Value
Battery2
Connected
Yes
NOTE
If
N
battery strings are
connected, set
Battery 1
Connected
to
Battery
N
Connected
to
Yes
, and set
the other parameters to
No
.
Rated Capacity 100 Ah
Rated capacity of the
batteries in a battery
string.
NOTE
The batteries connected to
one circuit breaker or fuse
are called a battery string.
BLVD Enable
Yes
Yes, No
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 100 Ah batteries in series), set
Battery1 Connected
and
Battery2 Connected
to
Yes
and
others to
No
, and set
Rated Capacity
to
100 Ah
.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 100 Ah batteries in series), set
Battery1 Connected
to
Yes
and others to
No
, and set
Rated
Capacity
to
200 Ah
.
10.5 Setting Sensor Parameters
Set sensor parameters based on site requirements.
Table 10-4
Sensor parameter settings
Main
Menu
Second-
Level
Menu
Third-
Level
Menu
Fourth-Level Menu Default Value Setting
Parameters
Settings
Power
System
Sensor
Config. Para.
Water Sensor
None
Set to Yes
or No as
required.
Smoke Sensor
None
Ambient Temp.
Sensor
None
Ambient Humi.
Sensor
None