TP48120A-HD15A1, TP48120A-HD15A2,
TP48200A-HD15A1, and TP48200A-HD15A2 Telecom
Power
User Manual
2 Overview
Issue 03 (2020-01-04)
Copyright © Huawei Technologies Co., Ltd.
18
Item
TP48120A-
HD15A1
TP48120A-
HD15A2
TP48200A-
HD15A1
TP48200A-
HD15A2
Application
environment
Class C
Class B
Class C
Class B
Heater
None
500 W heater
None
500 W heater
Rectifier
A maximum of four R4830N2s
A maximum of four R4850N2s
Maximum
output current
120 A
200 A
Capacity
≥ 55 W/K
≥ 85 W/K
Heat dissipation
Equipment compartment: heat exchanger
Battery compartment: direct ventilation
SMU
SMU06C
Sensor
Mandatory: battery temperature sensor
Optional: smoke sensor, temperature and humidity sensor, and water sensor
Lamp
Optional
Batteries
A maximum of two front-access battery strings (12 V/150 Ah)
Class B environments refer to indoor environments in which the ambient temperature and humidity
are not controlled and outdoor environments (with simple shielding measures) where humidity
sometime can occasionally reach 100%.
Class C environments refer to sea environments or outdoor land environments (with simple
shielding measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km
away from salt water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such
as smelteries, coal mines, and thermal power plants, 2 km away from medium pollution sources,
such as chemical, rubber, and galvanization industries, and 1 km away from light pollution sources,
such as packing houses, tanneries, and boiler rooms.