10 Commissioning
Issue 01 (2013-10-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
Step 2
Set the IP address, subnet mask, and gateway on the LCD, as shown in
Table 10-6
IP parameters
Main
Menu
Second-
Level Menu
Third-Level
Menu
Default Value
Setting
Setting
Wizard
Network
Parameters
IP Address
192.168.0.10
Set this parameter according to
the IP address assigned by the
network administrator.
Subnet Mask
255.255.255.0
Set this parameter according to
the subnet mask provided by the
network administrator.
Default Gateway
192.168.0.1
Set this parameter according to
the gateway address provided by
the network administrator.
Step 3
Set the
IP Addresses
and
Ports
for the active and standby servers of the NetEco on the LCD,
as described in
Table 10-7
NetEco parameters
Main
Menu
Second-
Level Menu
Third-Level
Menu
Fourth-Level
Menu
Default Value
Setting
Parameters
Settings
Comm.
Parameters
Network
Parameters
NetEco Primary IP
192.168.0.10
Set an IP address
for the active
NetEco server.
NetEco Backup IP
192.168.0.10
Set an IP address
for the standby
NetEco server.
NetEco Port
Number
31220
Set a port for the
NetEco.
----End
Networking Mode 2: over RS485 Port
Step 1
Check that the following parameters are set properly:
Port Mode
to
Manual
,
Protocol Type
to
M/S Protocol
,
Baud Rate
to
9600
, and
Comm. Address
to
3
.
Table 10-8
Communications parameters
Main Menu Second-
Level Menu
Third-Level
Menu
Fourth-
Level Menu
Fifth-Level
Menu
Default
Value
Setting
Parameters
Comm.
Serial Port
Northbound
Port Mode
Manual
Manual