Category
Tools and Instruments
Measuring tape
Bubble or digital level
Hydraulic pliers
Heat shrink tubing
Heat gun
N/A
PPE
Safety gloves
Safety goggles
Anti-dust respirator
Safety shoes
N/A
N/A
4.3 Determining the Installation Position
Basic Requirements
The SUN2000L is protected to IP65 and can be installed indoors or outdoors.
Do not install the SUN2000L in a place where a person can be easy to come into contact
with its enclosure and heat sinks, because these parts are extremely hot during operation.
Do not install the SUN2000L in areas with flammable or explosive materials.
Do not install the SUN2000L at a place within children's reach.
The SUN2000L will be corroded in salt areas, and the salt corrosion may cause fire. Do
not install the SUN2000L outdoors in salt areas. A salt area refers to the region within
500 meters from the coast or prone to sea breeze. The regions prone to sea breeze vary
depending on weather conditions (such as typhoons and monsoons) or terrains (such as
dams and hills).