SUN2000-(33KTL, 36KTL, 40KTL)-US
User Manual
5 Connecting Cables
Issue 07 (2019-06-20)
Copyright © Huawei Technologies Co., Ltd.
43
Figure 5-2
Connecting a ground cable
(1) Reserved PE point
----End
Follow-up Procedure
To enhance the corrosion resistance of the ground terminal, apply silica gel or paint on the
ground terminal after connecting the ground cable.
5.2.2 PV Side Grounding
Prerequisites
A ground cable and an OT terminal are available.
Recommended ground cable: an outdoor copper-core cable with a cross-sectional area of
6 AWG or more
OT terminal: M6
Procedure
Step 1
Prepare the OT terminal.
Step 2
Secure the ground cable using the ground screw.