Carrier Requirements
The carrier where the SUN2000 is installed must be fireproof.
Do not install the SUN2000 on flammable building materials.
Ensure that installation surface is solid enough to bear the SUN2000.
In residential areas, do not install the SUN2000 on gypsum boards or walls made of
similar materials which have a weak sound insulation performance because the noises
generated by the SUN2000 disturb residents.
Installation Angle Requirements
The SUN2000 can be installed on a wall, normal support, and tilted support.
Tilt requirements for installing a SUN2000 on a wall and normal support:
Install the SUN2000 vertically or at a maximum back tilt of 15 degrees to facilitate heat
dissipation.
Do not install the SUN2000 at a front tilt, excessive back tilt, side tilt, horizontally, or
upside down.
Figure 4-2
Wall-mounted installation and normal support-mounted installation
Tilt requirements for installing a SUN2000 on a tilted support:
Install the SUN2000 vertically or at a maximum back tilt of 75 degrees to facilitate heat
dissipation.
Do not install the SUN2000 at a front tilt, excessive back tilt, side tilt, horizontally, or
upside down.