Alarm
ID
Alarm Name
Alarm
Severity
Possible Causes
Troubleshooting
2051
Abnormal
Residual
Current
Major
Cause ID = 1
The insulation impedance
of the input side to PE
decreases when the
SUN2000 is operating.
1. If the alarm occurs
occasionally, the
external circuit may be
abnormal temporarily.
The SUN2000
automatically recovers
after the fault is
àì²Ēȇ
2. If the alarm occurs
frequently or persists,
check whether the
impedance between the
PV string and the
ground is too low.
2062
Low Insulation
Resistance
Major
Cause ID = 1
ɲ ä¯Ñàì²àñ²ìÑñàä
between the PV array
and the ground.
ɲ f¯É²Êì²àÑ©ì¯
PV array is damp and
the insulation between
the PV array and the
ground is poor.
1. Check the output
impedance of the PV
array to ground. If there
is a short circuit or lack
of insulation, rectify it.
2. Check that the PE cable
of the SUN2000 is
correctly connected.
3. If the impedance is
lower than the äݲĒ
protection threshold in
rainy and cloudy days,
set Insulation
resistance protection
using the mobile app,
SmartLogger, or NMS.
Current insulation
àä²äìÊǿĂDƐȀ
possible short circuit
ÝÑä²ì²ÑÊǿĂɟȇf¯ä¯Ñàì
circuit position is valid
for a single PV string. If
there are multiple PV
strings, check the PV
strings one by one. For
details, see
E Locating
Insulation Resistance
Faults
.
SUN2000-(2KTL-6KTL)-L1
User Manual
8 System Maintenance
Issue 03 (2020-09-15)