background image

6

5. After the green indicator of the BCU blinks at super short intervals and the red indicator is 

steady on, switch on the battery circuit breaker on the battery cabinet.

Switch off the battery circuit breaker in the battery cabinet. (If multiple 

SmartLi cabinets are connected in parallel, perform this operation on 

each cabinet.)

Press and hold the POWER ON/OFF button on the BCU for more than 5s until 
all the three indicators blink to power off the system. (If multiple SmartLi
cabinets are connected in parallel, perform this operation on each cabinet.)

Copyright ©  Huawei Digital Power Technologies Co., Ltd. 
2022. All rights reserved.

08

Power-Off

Item

Description

Default Value Value Range

Application scenario

Specifies the SmartLi connection scenario.
Currently, the UPS and EHU scenarios are 
supported.

UPS

UPS, HVDC, 
EHU, SST

Number of lead-acid 
batteries supported
(The value of this 
parameter must be 
the same as the 
setting of Batteries 
in a battery string
on the UPS 
monitoring screen.)

When the SmartLi is connected to the UPS 
without communication, the UPS manages 
the SmartLi based on the lead-acid battery 
logic. You need to set the number of lead-
acid batteries supported for the UPS on 
the SmartLi monitoring screen to ensure 
that the charge and discharge operating 
voltage ranges of the UPS and SmartLi
match each other.
By default, Number of lead-acid 
batteries supported 
is set based on the 
single battery voltage (2 V). If the single 
battery voltage in the UPS system is 12 V, 
convert it to 2 V before setting this 
parameter. For example, if the single 
battery voltage is 12 V and the number of 
batteries in a battery string is 42, the value 
of Number of lead-acid batteries 
supported 
is 252 (42 x 12/2 = 252) in the 
7+7/7+0 scenario.

8+8/8+0 
scenario: 276

8+8/8+0 
scenario: 276–
300

7+7/7+0 
scenario: 252

7+7/7+0 
scenario: 240–
270

6+6/6+0 
scenario: 204

6+6/6+0 
scenario: 192–
234

Battery cabinet 
quantity

Specifies the number of battery cabinets 
connected in parallel.
Currently, a maximum of 10 lithium 
battery cabinets can be connected in 
parallel.

1

1–10

Altitude (m)

Set this parameter based on the altitude of 
the place where the rack is used.

≤ 1000

≤ 1000, 1000–
2000, 2000–
3000, 3000–
4000

Chg. cur. limiting 
coef. (C)

You can set a charge current limit. The 
limiting coefficient is a multiple of the 
battery capacity.

0.5

0.05–1.00

Cell undervoltage
protection threshold 
(V)

You can adjust the end-of-discharge (EOD) 
threshold as required.

2.7

2.5–2.8

Battery 
undervoltage
protection time (h)

Specifies the maximum battery discharge 
time.

8

8–3000

Maintenance period 
(y)

Specifies the interval for reminding users 
of battery maintenance.

0

0–10

Last maintained at

After the maintenance is complete, you 
can set the time as a reference for the 
next maintenance.

-

-

SmartLi 3.0 Quick Guide (Short-Term Backup Power)

If battery modules will be stored for a long time after power-off, remove the BCU to 
reduce battery discharge. This prevents battery modules from being overdischarged due 
to storage at low SOC.

If battery modules are stored without being fully charged, charge them according to the 
requirements  in "Operations > Recharge Requirements  for Batteries with Low SOC" to 
prevent battery module damage due to overdischarge.

When you hold the button to power off a cabinet, only the indicators on the cabinet 
where the software version is later than V500R022C00SPC100  will blink.

The preceding procedure applies to the single-cabinet scenario. For the multi-cabinet 
scenario, see 

SmartLi 3.0 User Manual (Short-Term Backup Power)

.

Содержание SmartLi-512V-162Ah-F

Страница 1: ...ncluding the Insulation Layer Unit mm Recommended Cable Size Unit mm2 M40 10 32 Innermost layer white 10 16 Innermost layer white second to last layer red 16 22 70 95 120 The single core 90 C resistant flexible copper cable is used as an example in the table to illustrate which sealing plugs need to be removed The sealing plugs to be removed depend on the actual cable diameter including the insula...

Страница 2: ...nd crimp the DT terminal Marked DT terminal direction Marked cable cutting position 1 Set the switch based on the actual load Installing Output Power Cables 250 kW Load of a single battery cabinet 300 kW 200 kW Load of a single battery cabinet 250 kW Load of a single battery cabinet 200 kW 2 Install power cables UPS Without a Neutral Wire UPS With a Neutral Wire Connect cables correctly to avoid b...

Страница 3: ...battery strings and the cabinet It is recommended that you use the DC voltage mode of a multimeter to measure the voltage between the battery tray and the positive and negative terminals of each battery string respectively If the readings are less than 6 V DC the insulation is good Otherwise contact technical support engineers 8 Attach PP sheets to the notches of the battery modules on the top lay...

Страница 4: ...easures for example using a dust cover plastic film or fabric cloth to prevent battery condensation or dust corrosion Remove the protective material when batteries need to be used The BCB off alarm the red indicator is steady on is displayed on the SmartLi LCD No action is required After the battery circuit breaker is switched on the alarm will be automatically cleared The green indicator blinks i...

Страница 5: ...when the discharge current is 0 1C 0 3C 0 5C or 1 0C respectively 1 8 Dis cur 0 3C EOD V cell 1 8 Dis cur 0 5C EOD V cell 1 75 Dis cur 1 0C EOD V cell 1 75 If a third party UPS is connected and the EOD is not distinguished by rate set this parameter to 1 8 V cell If a third party UPS is connected set this parameter to the maximum value If the UPS from the Company is connected set Batt charging cap...

Страница 6: ... Number of lead acid batteries supported is 252 42 x 12 2 252 in the 7 7 7 0 scenario 8 8 8 0 scenario 276 8 8 8 0 scenario 276 300 7 7 7 0 scenario 252 7 7 7 0 scenario 240 270 6 6 6 0 scenario 204 6 6 6 0 scenario 192 234 Battery cabinet quantity Specifies the number of battery cabinets connected in parallel Currently a maximum of 10 lithium battery cabinets can be connected in parallel 1 1 10 A...

Отзывы: