SmartLi 3.0 Quick Guide (Short-Term Backup Power)

06

Verifying the Installation

Do not remove the dust cover 
before power-on.

Item

Acceptance Criteria

Cabinet 
installation

The cabinet is securely installed and does not tilt due to vibration.

Neat arrangement

The adjacent cabinets are neatly arranged and secured with connecting kits.

Cable layout

Cables are routed properly as required by the customer.

Cable labels

Both ends of a cable are labeled. Labels are concise and easy to understand.

Cable ties

Cable ties are secured evenly and no burr exists.

Cable or copper 
bar connections

Battery cables or copper bars are securely connected, the spring washers are 
crimped properly for cables secured by screws, and the cables are intact.

Grounding

The resistance between the cabinet ground bar and the equipment room 
ground bar is less than 0.1 ohm.

Battery cable 
connections

1.The cabinet is correctly connected to the UPS.
2.Battery cabinets in parallel are correctly connected.
3.The battery neutral wire (if any) is correctly connected.

Short-circuit at 
the upstream and 
downstream of 
circuit breakers

Check whether there is a short circuit between the positive, neutral, and 
negative cables for circuit breakers, between copper bars, and between the 
cables, copper bars, and enclosure. If there is a short circuit, check whether 
the cables are damaged or short-circuited. If yes, repair the cables.

Foreign matter 
cleaning inside 
the cabinet

The inside and outside of the cabinet are free from conductive dust or other 
sundries.
1.There is no foreign matter (such as copper wires and screws) on the top 

of the cabinet.

2.There is no foreign matter on the copper bar terminals.
3.There is no foreign matter around circuit breaker terminals.
4.There is no foreign matter on the bottom plate of the cabinet.
5.There is no foreign matter on the rear module subrack.

Cover installation

All the covers are reinstalled  after checks are performed.

Storage 
environment

After the installation is complete, do not store the equipment in an 
environment where the temperature  and humidity are uncontrollable  for a 
long period of time. Otherwise, the equipment may be damaged due to 
condensation.

Insulation 
resistance of 
output power 
cables

The battery cabinet output cables are intact. The insulation resistance of the 
positive, negative, and neutral output cables to the ground and that 
between the positive, negative, and neutral output cables are greater than 2 
megohms (using a 500 V megohm meter).

Installation 
protection

If batteries are not powered on after installation, take dustproof and anti-
condensation measures (for example, using a dust cover, plastic film, or 
fabric cloth) to prevent battery condensation or dust corrosion. Remove the 
protective material when batteries need to be used.

The BCB off alarm (the red indicator is steady on) is displayed on the SmartLi LCD. No action is 
required. After the battery circuit breaker is switched on, the alarm will be automatically cleared.

The green indicator blinks intermittently.  After 1 minute, the BCU starts. The green indicator blinks at 
super short intervals and the red indicator is steady on.

1. Press and hold the POWER ON/OFF button on the BCU of the SmartLi cabinet for more than 2s. The 

green indicator of the BCU blinks at short intervals.

Status of Indicators on the BCU

Description

The green indicator blinks at 4 Hz (at short intervals).

Status after the switch button is pressed.

The green indicator blinks on for 1s and off for 4s 
(intermittently).

The SmartLi circuit breaker cannot be switched on, 
and the UPS cannot be cold started.

The green indicator blinks at 10 Hz (blinking at super 
short intervals), and the red indicator is steady on.

The SmartLi circuit breaker can be switched on, but 
the UPS cannot be cold started.

The green indicator blinks at 1 Hz or is steady on 
(blinking at long intervals).

The UPS can be cold started.

3. Set the language, time, date, cloud service, network parameters, system 

parameters, and alarm parameters on the Settings Wizard screen of the SmartLi.

Turn on the ready switch on the BCU.

Ensure that the UPS runs stably in normal mode and the rectifier shown in the energy flow diagram is started.

Item

Description

Default 
Value

Value Range

Application scenario

Specifies the SmartLi connection 
scenario.
Currently, UPS scenarios are 
supported.

UPS

UPS, HVDC, 
EHU, SST

Battery cabinet 
quantity

Specifies the number of battery 
cabinets connected in parallel.
Currently, a maximum of 10 lithium 
battery cabinets can be connected 
in parallel.

1

1–10

Cell undervoltage
protection threshold 
(V)

You can adjust the end-of-
discharge (EOD) threshold as 
required.

2.7

2.5–2.8

Battery 
undervoltage
protection time (h)

Specifies the maximum battery 
discharge time.

8

8–3000

Maintenance period 
(y)

Specifies the interval for reminding 
users of battery maintenance.

0

0–10

Last maintained at

After the maintenance is complete, 
you can set the time as a reference 
for the next maintenance.

First power-
on time

2000-01-01 
to 2037-12-
31

Communicating with the UPS

The UPS supports communication with SmartLi 3.0 and a communications cable is correctly 
connected between the UPS and the SmartLi.

2. Obtain authorization on the battery cabinet.

07

Power-On

System User

LCD Preset 
Password

WebUI Preset 
Password

admin (administrator)

000001

Changeme

operator (common user) 000001

Changeme

To ensure system security, 
change the preset 
password after login.

Содержание SmartLi-512V-162Ah-F

Страница 1: ...ncluding the Insulation Layer Unit mm Recommended Cable Size Unit mm2 M40 10 32 Innermost layer white 10 16 Innermost layer white second to last layer red 16 22 70 95 120 The single core 90 C resistant flexible copper cable is used as an example in the table to illustrate which sealing plugs need to be removed The sealing plugs to be removed depend on the actual cable diameter including the insula...

Страница 2: ...nd crimp the DT terminal Marked DT terminal direction Marked cable cutting position 1 Set the switch based on the actual load Installing Output Power Cables 250 kW Load of a single battery cabinet 300 kW 200 kW Load of a single battery cabinet 250 kW Load of a single battery cabinet 200 kW 2 Install power cables UPS Without a Neutral Wire UPS With a Neutral Wire Connect cables correctly to avoid b...

Страница 3: ...battery strings and the cabinet It is recommended that you use the DC voltage mode of a multimeter to measure the voltage between the battery tray and the positive and negative terminals of each battery string respectively If the readings are less than 6 V DC the insulation is good Otherwise contact technical support engineers 8 Attach PP sheets to the notches of the battery modules on the top lay...

Страница 4: ...easures for example using a dust cover plastic film or fabric cloth to prevent battery condensation or dust corrosion Remove the protective material when batteries need to be used The BCB off alarm the red indicator is steady on is displayed on the SmartLi LCD No action is required After the battery circuit breaker is switched on the alarm will be automatically cleared The green indicator blinks i...

Страница 5: ...when the discharge current is 0 1C 0 3C 0 5C or 1 0C respectively 1 8 Dis cur 0 3C EOD V cell 1 8 Dis cur 0 5C EOD V cell 1 75 Dis cur 1 0C EOD V cell 1 75 If a third party UPS is connected and the EOD is not distinguished by rate set this parameter to 1 8 V cell If a third party UPS is connected set this parameter to the maximum value If the UPS from the Company is connected set Batt charging cap...

Страница 6: ... Number of lead acid batteries supported is 252 42 x 12 2 252 in the 7 7 7 0 scenario 8 8 8 0 scenario 276 8 8 8 0 scenario 276 300 7 7 7 0 scenario 252 7 7 7 0 scenario 240 270 6 6 6 0 scenario 204 6 6 6 0 scenario 192 234 Battery cabinet quantity Specifies the number of battery cabinets connected in parallel Currently a maximum of 10 lithium battery cabinets can be connected in parallel 1 1 10 A...