Figure 9-28
Installing CPRI optical cables for single-fiber bidirectional optical modules
Step 3
Route the cables according to the instructions in
cable ties to bind the cables.
Step 4
Label the installed cables according to the instructions in Attaching an L-Shaped Label.
----End
9.12 Closing the Cover Plate of an RRU Cabling Cavity
This section describes the procedure for closing the cover plate of an RRU cabling cavity.
Procedure
Step 1
Close the clips for the installed cables. Use an M4 torque screwdriver to tighten the screws on
each clip to 1.4 N·m (12.39 lbf·in.), as shown in
NOTICE
Ensure that the exposed shield layer of the power cable is properly tightened using the clip.
RRU3260
Installation Guide
9 Installing RRU Cables
Issue 10 (2015-12-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
113