4 Electrical Connections
Issue 02 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
19
The general power input cable of the SUN2000 communication box needs to be prepared by the
customer. Recommended cable: four-core multi-wire armored; operating voltage to the ground: ≥
600 V; operating voltage between cables: ≥ 1000 V; cross-sectional area of a single core: 4 mm
2
.
The cable from the busbar to the knife switch needs to be prepared by the customer. Recommended
cable: three-core multi-wire; operating voltage to the ground: ≥ 600 V; operating voltage between
cables: ≥ 1000 V; cross-sectional area of a single core: 4 mm
2
.
Table 4-2
describes the components to be configured in a SUN2000 communication box
scenario.
Table 4-2
Components to be configured in a SUN2000 communication box scenario
Component
Model or
Specifications
Quantity
PLC CCO
PLC CCO01A
1 PCS
Data collector
SmartLogger1000
1 PCS
Knife switch
Fuse
Rated voltage: ≥ 600
V; rated current: 6 A
3 PCS
Knife switch box
Rated voltage: ≥ 600
V; rated current: ≥ 6
A; number of
phases: three
1 PCS
Figure 4-3
shows the cable routes for the PLC CCO used in a SUN2000 communication box.