35
Appendixes
1
Installing Power Cables for the C3 PDU
Installing and Routing the Power Cables
– DC Power Distribution Box
a
Power output area
Power switch area
Power input area
Item
Specifications
Input
power
Rated input voltage
-48 V DC to -60 V DC
Input voltage range
-38.4 V DC to -72 V DC
Input mode
2 DC power inputs from different power facilities
Maximum input current
A maximum of 80 A current for each power input
Input terminal type
M8 OT terminal
Output
power
Rated output voltage
-48 V DC to -60 V DC
Output voltage range
-38.4 V DC to -72 V DC
Number of power outputs
Eight power outputs under control of four circuit breakers.
For the OptiX RTN 980 equipment, one circuit breaker is
required to control one power output.
Maximum current of each circuit
breaker
40 A
Output protection
The overcurrent protection function is available, but
manual recovery is required.
Output terminal type
Cord end terminal (12-10AWG)
A
-
48
V
-
48
V
G
N
D
G
N
D
-
48
V
-
48
V
G
N
D
G
N
D
-
48
V
-
48
V
G
N
D
G
N
D
-
48
V
-
48
V
G
N
D
G
N
D
S
W
1
S
W
2
S
W
3
S
W
4
SW1
SW2
SW3
SW4
Power switch area
A