10
Connecting an FE teamwork network cable
•
All smart cooling products in a teamwork group must be of the same model.
•
Do not directly connect the first and the last smart cooling products to form a ring network.
•
A maximum of 32 smart cooling products can be networked in one group. The teamwork
cable between two adjacent smart cooling products must not exceed 10 m.
•
If CAN networking is required onsite, set
Enable teamwork CAN resistor
for the first and last
smart cooling products to
Yes
on the screen.
Connect one end of the FE network cable to the
FE port on the main control module, connect the
other end to the POE port on the smart ETH
gateway.
CAN teamwork networking cable
1. Prepare the 8 pin standard network cable, the cable pin sequence requirements are shown
below.
2. Connect the CAN_OUT port of each smart cooling product to the CAN_IN port of the following
smart cooling product using a CAN network cable. After powering on the device, set the
Enable
teamwork CAN resistor
to
Yes
for the first and last devices in a teamwork group.