19
Connecting the Equipotential Bonding Cable
7.4
Equipotential bonding point
(Optional) Connecting a Differential Pressure Sensor
7.5
1. Secure the differential pressure sensor inside the cabinet using two M3 screws.
2. Connect the longer PU hose to the port without the
Lo (-)
silk screen under the differential
pressure sensor, and route the hose through the top of the cabinet to the supply air pipe
plenum chamber. (There should be two binding points adjacent to the pressure inlet. The
distance between the binding point closer to the pressure inlet and the pressure inlet should
not exceed 25 mm, and the distance between two binding points is within 20
–30 mm.)
3. Connect cables to the differential pressure sensor.
4. After powering on the NetCol8000, choose
Settings
>
System Settings
>
Indoor Fan
, and
set
Air-side difference pressure sensor type
to
0
–500 Pa
.
NetCol8000-A045 Upflow
NetCol8000-A045/A090 Downflow