24
(Optional) Installing the Cap (Applicable to Upflow Units)
7.10
It takes two persons to install the cap using a 2 m step ladder.
Before installing the cap, attach the thermal insulation foam in the accessories to the top beam
of the smart cooling product, and ensure that the reserved holes in the thermal insulation foam
are aligned with the holes in the beam. Check that the cap is intact and free from scratches, that
the sheet metal is not bent, and that the screws are secure.
1. Remove the cap front panel using a Phillips screwdriver. Place the cap on the top of the cabinet.
2. Secure the left and right sides of the cap using six M5 screws and the front and rear of the cap
using four M5. screws.
3. Secure the cap front panel to the frame, and adjust the angle of the front panel blade.