Figure 4-26 Setting the external IP address of the MU
NO TE
Set MUNNatIP to the external IP address of the IVS1800, which is the same as the
external IP address mapped by the IVS1800 on the ECC800-Pro.
6. Set Module Name to OMU and click Search.
7. In the search result, click Edit in the row where the value of Parameter Name
is OMUNNatIP and set Value to the MUNNatIP address of the MU. Click
Save.
Figure 4-27 Setting the external IP address of the OMU
Step 5 Enable camera NTP synchronization.
The camera NTP synchronization function for the server is disabled by default. The
camera NTP synchronization function needs to be enabled for the server that
connects to the camera. After the camera NTP synchronization function is enabled,
cameras will automatically time-synchronize from their access servers.
1. Log in to the OMU portal as the admin user.
2. Choose Maintenance > Unified Configuration.
3. Set Module Name to SCU and Parameter type to System property, and
click Search.
4. In the search results, click Edit in the row where Parameter Name is NTPIPC
and set Value to 1.
IVS1800 Video Management System
User Manual
4 Commissioning the IVS1800
Issue 02 (2021-01-27)
Copyright © Huawei Technologies Co., Ltd.
45