5 System Commissioning
Issue 07 (2019-12-30)
Copyright © Huawei Technologies Co., Ltd.
55
Figure 5-16
Settings page
Keep
IP Address
consistent with the iBOX IP address and set the port to
502
.
If
ModbusTCP encryption
and
ModbusTCP authentication
on the iBOX WebUI are set to
Disable
, select
Non-SSL Connection
for
Connection Mode
. If
ModbusTCP encryption
and
ModbusTCP authentication
are set to
Enable
, select
SSL Connection
for
Connection Mode
.
When multiple iBOXs are connected in parallel, you need to set parameters on the NetEco for each
iBOX.
Step 5
Click
Connection Test
and save the setting after a message indicating successful connection
appears.
----End
5.5 Networking the iBOX and iBAT
Context
Parameters have been set depending on the preceding scenarios.
If the UPS does not charge batteries for a long time, power off the iBOXs to prevent damage
to batteries. After an iBOX has powered off for 30 minutes, the iBATs automatically
hibernate.
An iBAT hibernates automatically under the following conditions:
The iBAT has failed to communicate with the iBOX for more than 30 minutes.
The iBAT has not been networked successfully more than two days after power-on.