![background image](http://html.mh-extra.com/html/huawei/ibattery-3-0/ibattery-3-0_user-manual_166620057.webp)
iBattery 3.0
User Manual
5 System Commissioning
Issue 07 (2019-12-30)
Copyright © Huawei Technologies Co., Ltd.
51
Table 5-1
Setting iBOX parameters
Parameters
Description
Remarks
iBOX single
battery qty.
Total number of batteries monitored
by the iBOX.
Set according to the battery
parameters planned by the
customer.
Batt installation
time
Actual time at which batteries are
installed.
N/A
Battery string
capacity
Capacity of a single battery
multiplied by the number of battery
strings.
Obtain the battery capacity
from the battery label or
document.
Current source
Select a Hall effect sensor (xxx A).
The actual specifications of the Hall
effect sensor will apply.
The actual specifications of
the Hall effect sensor prevail.
Battery string No.
The serial number of each battery
string. Set this parameter based on
the planned codes for iBOXs and
battery strings. The
Battery string
No.
are unique for a same UPS.
Set according to the
customer plan.
BCB tripping upon
battery abnormal
If the BCB box is configured, set
BCB tripping upon battery
abnormal
to
Enable
.
N/A
If multiple iBOXs are connected, commission the iBOX one by one in the same way. Otherwise,
networking may be in disorder.
----End
5.4 Setting Parameters for the Scenario Where the iBOX
Connects to the NetEco
Procedure
Step 1
Set iBOX parameters.
1.
On the iBOX WebUI, choose
System Settings > Batt. String Config
, and set
Batt.
String Config
.