iBattery 3.0
User Manual
5 System Commissioning
Issue 07 (2019-12-30)
Copyright © Huawei Technologies Co., Ltd.
53
Running
Parameter
Description
Parallel
Communication
Configuration
This parameter needs to be set when multiple iBOXs are connected
in parallel and does not need to be set when there is only one
iBOX. Set
Whether the iBOX communicates directly with the
NetEco
to
Yes
, and set
Number of iBOX configured under each
UPS
. Configure IP addresses for multiple iBOXs.
Modbus Config
Set ModbusTCP encryption and ModbusTCP authentication,
which are consistent with Connection Mode on the NetEco.
HALL Reverse
Config
If the Hall effect sensor is reversely installed, you can set reverse
connection to correct it.
Basic Information
If a BCB box is configured, set
BCB configuration
to
Done
and
Batt. abnormal BCB trip
to
Enable
.
3.
On the
System Settings
page, set
Time
,
IP Address
,
Battery Curve
and
Parallel Net
Join Config
.
Figure 5-12
Time
Figure 5-13
IP Address