3
• Install Hall effect sensors. If the battery string has a neutral wire, install a Hall effect sensor on
each of the positive and negative cables. If the battery string does not have a neutral wire, install
a Hall effect sensor on the positive or negative cable.
• The arrow direction of the Hall effect sensor must be the same as the current direction when the
batteries are being charged. It is not recommended to install Hall inside BCB box.
• If the positive (negative) terminal of a battery string has multiple cables, multiple Hall effect
sensors are required.
Installing Hall Effect Sensors
2.2
2. Insert the terminal into the iBAT port with force, and ensure that it is securely connected.
3. Attach the iBAT to the top or side of the battery based on the battery installation space. Press
the iBAT with your palm for more than 10 seconds to ensure that it is attached firmly and evenly.
With a neutral wire
Cable Label
iBOX Port
B_HALL1
HALL_1
Battery1-_HALL2
HALL_2
B_HALL3
HALL_3
Battery2-_HALL4
HALL_4
B_HALL5
HALL_5
Battery3-_HALL6
HALL_6
B_HALL7
HALL_7
Battery4-_HALL8
HALL_8
Cable Label
iBOX Port
B_HALL1
HALL_1
B_HALL2
HALL_2
Battery1-_HALL3
HALL_3
Battery1-_HALL4
HALL_4
B_HALL5
HALL_5
B_HALL6
HALL_6
Battery2-_HALL7
HALL_7
Battery2-_HALL8
HALL_8