6.2 Environment specifications
Table 6-2 Environmental specifications
Category
Specifications
Temperature
● Operating temperature: 5°C to 40°C (41°F to 104°F)
(ASHRAE Classes A2 and A3 compliant)
● Storage temperature (≤ 72 hours): –40°C to +65°C
(–40°F to +149°F)
● Long-term storage temperature (> 72 hours): 21°C
to 27°C (69.8°F to 80.6°F)
● Maximum temperature change rate: 20°C/h (36°F/h)
NOTE
If Intel
®
Xeon
®
Scalable processors (Platinum 8180, 8180M,
8168 or Gold 6144, 6146, 6154) are used, the maximum
operating temperature supported is 35°C (95°F).
Relative humidity (RH,
non-condensing)
● Operating humidity: 5% to 85%
● Storage humidity (≤ 72 hours): 5% to 95%
● Long-term storage humidity (> 72 hours): 30% to
69%
● Maximum change rate: 20%/h
Altitude
● Operating altitude ≤ 3050 m (10006.44 ft)
– If the server complies with ASHRAE Class A2, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 300 m (984.25
ft) in altitude above 900 m (2952.76 ft).
– If the server complies with ASHRAE Class A3, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 175 m (574.15
ft) in altitude above 900 m (2952.76 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month