21
Verify the Installation
Item
Check That
Check Result
Cabinet
The cabinet position is consistent with the equipment room layout
diagram.
□ Passed □ Failed
All bolts and screws are firmly tightened, especially on electrical
connections. Flat and spring washers are used with each bolt, and
spring washers are placed on the top of flat washers.
□ Passed □ Failed
The cabinet is clean and complies with dustproof requirements.
□ Passed □ Failed
All labels are correct, clear, and complete.
□ Passed □ Failed
The paint on the cabinet exterior is intact. Promptly repaint the
cabinet exterior if necessary to prevent corrosion.
□ Passed □ Failed
The cabinet door and lock work properly.
□ Passed □ Failed
The cabinet has no waste tape, cable ties, paper, or packing
materials around it.
□ Passed □ Failed
All components are properly installed and no component is left
onsite.
□ Passed □ Failed
Empty cable holes are blocked using plugs or lids.
□ Passed □ Failed
Cable
All cable connections are secure, especially network cable
connections.
□ Passed □ Failed
Exposed parts of cables and cable lugs near the cable terminals
are wrapped with insulation tape or heat-shrink tubing.
□ Passed □ Failed
Flat washers and spring washers of all wiring terminals are
securely installed and in good contact.
□ Passed □ Failed
Cables are bound neatly, and cable ties are secured evenly and
properly in the same direction.
□ Passed □ Failed
Excess sections of cable ties are neatly cut.
□ Passed □ Failed
There is no unnecessary adhesive tape or cable tie on cables.
□ Passed □ Failed
Routed cables are convenient for future maintenance and
expansion.
□ Passed □ Failed
Labels at the cable ends are clear.
□ Passed □ Failed
Electrical
All ground cables are copper cables with diameters meeting the
requirements. No switch or fuse is allowed on a ground cable, and
no open circuit occurs.
□ Passed □ Failed
All ground cables, AC input cables, and intra-cabinet cables are
connected correctly according to the power system circuit
diagram, and all screws are fastened. The input and output cables
are not short-circuited.
□ Passed □ Failed
The smart cooling product input voltage is within the range of
rated voltage
±
10%, and the input frequency is within the range
of rated frequency
±
3 Hz.
□ Passed □ Failed
Power cables and ground cables are not coiled and excess parts
are cut off.
□ Passed □ Failed
Lugs for power cables and ground cables are welded or crimped
securely.
□ Passed □ Failed
Power cables and ground cables are routed and bound separately
from other cables.
□ Passed □ Failed
Lithium batteries are intact, free from damage, cracks, and bulges. □ Passed □ Failed
Lithium batteries are neat and clean, and do not leak electrolyte.
□ Passed □ Failed
Lithium battery terminals are upright and free from damage,
break, and acid leakage.
□ Passed □ Failed
The lithium battery cables are correctly connected.
□ Passed □ Failed
DIP switches on devices are correctly set.
□ Passed □ Failed