1
Copyright © Huawei Technologies Co., Ltd. 2020.
All rights reserved.
Product Overview
The component layout is for reference only. The actual
installation positions of the components may vary.
Item
Specifications
Cabinet dimensions (H x W x D)
(unit: mm)
Converged Cabinet: 2000 x 600 x 1350
Installation scenario
Supports only a single cabinet.
Installation space
The cabinet provides 42 U available space. The mounting
bars are adjustable, and space is reserved at the rear of the
cabinet for installing half-height rPDUs vertically.
Power distribution
6 kVA UPS
rPDU: Only half-height vertical rPDUs are supported.
Lithium battery: 100 Ah/48 V DC
Operating temperature
Indoor: 0
°
C to 40
°
C; outdoor: –20
°
C to +45
°
C
Operating humidity
5%–95% RH
IP rating
IP20
Maximum power of a single cabinet
3 kW
Installation mode
Installed on a concrete floor or an electrostatic discharge
(ESD) floor
Altitude
≤ 1000 m (derated when the altitude ranges from 1000 m
to 4000 m)
Component
Onsite Installation
ECC800-Pro
Not required
UPS
Not required
Lithium battery
Required
3.5 kW split-type air
conditioner
Required
Water sensor
Required
Temperature and humidity
(T/H) sensor
Required