![Huawei FusionDC1000A Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/huawei/fusiondc1000a/fusiondc1000a_maintenance-manual_168032119.webp)
Figure 4-58 Removing a point-type water sensor
Step 3 Install a new water sensor and tighten the screws.
NO TE
The gap between the water sensor and the floor is 2 mm.
Step 4 Connect cables to the water sensor.
Step 5 Check that the new water sensor is working properly.
NO TE
Drip a small amount of water onto the water sensor. If the monitoring software terminal
generates an alarm, the water sensor is working properly.
----End
4.3.8 Replacing Access Control System Components
4.3.8.1 Replacing a Card Reader
Prerequisites
A spare IC card reader of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: access card, spare IC card reader
Skill requirement: ELV engineer
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
4 Parts Replacement
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
111